2001-01-08 00:00:00P-400, I CAN NOT FIND A LOCATION AS TO
 WHERE THE STORM DRAIN BUBBLER DETAIL IS
 GOING TO BE BUILT.PLEASE CALL OUT THE
 EXACT LOCATION, SINCE THERE IS NO
 PRIVATE PROPERTY THIS CAN BE PLACED ON
 UNLESS IT IS IN THE DUMPSTER ENCLOSURE.
  
 THE FOLLOWING COMMENTS MAY NOT BE VALID
 SINCE IT IS MY UNDERSTANDING THAT THE
 ALLEYWAY PAVER AND LANDSCAPE PLAN HAS
 BEEN REDRAWN, BUT NOT SUBMITTED WITH
 THIS PLAN SET FOR REVIEW:
  
 SHEET SERIES L1.0, PAVER DESIGN DOES NOT
 MATCH EXISTING PAVERS WITH CIRCULAR
 DESIGN AT THE POINT OF CONNECTION
 BETWEEN DATURA AND THE ALLEY.
  
 THE EXISTING PLAN DOES NOT SHOW THE
 EXISTING PALM TREES.PERMISSION FROM
 THE CITY WILL BE REQUIRED TO PERMANENTLY
 REMOVE THE TREES.THE TREES NEED TO BE
 REMOVED DURING CONSTRUCTION BY THE
 CONTRACTOR TO SAFE GUARD THEM.OR
 REPLACED BY THE CONTRACTOR PRIOR TO
 RECEIVING YOUR CO.
  
 THE EXISTING IRRIGATION SYSTEM IS NOT
 SHOWN TO BE CUT BACK TO THE END OF THE
 LAST SERVICE TEE. WHICH IS REQUIRED IF
 THE TREES ARE NOT TO GO BACK IN AS SHOWN
 ON YOUR PLAN.
  
 THE ELECTRIC LINE TO THE TREE "UP
 LIGHTS" AND TO THE STATUE AT DATURA AND
 THE ALLEY NEEDS TO BE RECONFIGURED.IF
 THE TREES WILL NOT BE PUT BACK THOSE
 LINES NEED TO BE CUT OUT, BUT THE WIRING
 REMAIN.
  
 THE STATUE WILL NEED TO BE PROTECTED.
 YOU WILL NEED TO GET PERMISSION TO
 REMOVE IT TILL THE BUILDING IS NEAR
 COMPLETION.
  
 THE PLANTERS ON NARCISSUS WILL NOT HAVE
 TREE GRATES AND BURIED "UP LIGHTS".USE
 THE 1' HIGH GREEN FENCE AND PLANTS AS
 USED ON THE PLANTERS ON NARCISSUS NORTH
 AND SOUTH OF CLEMATIS.THE LIGHTS MUST
 BE ABOVE GROUND INSIDE THE PLANTERS.
  
 ADDITIONALLY DELETE THE GALVANIZED STEEL
 CHANNEL EDGE FOR THE TREE GRATES TO SIT
 IN.