Plan Review Notes
Plan Review Notes For Permit 99121640
Permit Number 99121640
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00SUBMIT COMPLETE GAS DRAWING FOR REVIEW.
 SHOW PIPE MATERIAL,ALL CUT SECTIONS OF
 PIPE,TOTAL BTU LOAD,AIR FOR COMBUSTION,
 VENT DETAIL,ETC.COMPLY W/SGC SECS.305.4,
 402.1,402.4,AND ALL APPLICABLE SECS.OF
 SGC AND NFPA 54.
  
 CLEARLY SHOW HOW EFFLUENT FROM PUMPS IN
 ELEVATOR SHAFT WILL BE DISPOSED.
  
 FIXTURE AND BRANCH DRAINS ON SOVENT
 SYSTEM SHALL COMPLY W/ASSE STANDARD
 #1043 SEC.3.2(E).(SEE BACK TO BACK LAVS)
  
 OCCUPANT LOAD REQD.FOR RESTAURANT TO
 ENSURE COMPLIANCE W/SPC TABLE 407 FOR
 MINIMUM FIXTURE REQS.
  
 THE SANITARY FACILITIES ON THE ROOF ARE
 IN COMPLIANCE W/FLA.DEPT.OF HEALTH
 CHAPT.64E-9.OO6(F) FOR THE OCCUPANT
 LOAD OF THE POOL AND SPA ONLY! ANY
 OTHER USE SUCH AS WEDDINGS,PARTIES,ETC.
 CONSTITUTES A VIOLATION OF THE STD.PLBG.
 CODE SEC.407.1.3.FOR NUMBER OF MINIMUM
 REQUIRED SANITARY FACILITIES.