Plan Review Notes For Permit 99121640 |
Permit Number |
99121640 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | SUBMIT COMPLETE GAS DRAWING FOR REVIEW. | | SHOW PIPE MATERIAL,ALL CUT SECTIONS OF | | PIPE,TOTAL BTU LOAD,AIR FOR COMBUSTION, | | VENT DETAIL,ETC.COMPLY W/SGC SECS.305.4, | | 402.1,402.4,AND ALL APPLICABLE SECS.OF | | SGC AND NFPA 54. | | | | CLEARLY SHOW HOW EFFLUENT FROM PUMPS IN | | ELEVATOR SHAFT WILL BE DISPOSED. | | | | FIXTURE AND BRANCH DRAINS ON SOVENT | | SYSTEM SHALL COMPLY W/ASSE STANDARD | | #1043 SEC.3.2(E).(SEE BACK TO BACK LAVS) | | | | OCCUPANT LOAD REQD.FOR RESTAURANT TO | | ENSURE COMPLIANCE W/SPC TABLE 407 FOR | | MINIMUM FIXTURE REQS. | | | | THE SANITARY FACILITIES ON THE ROOF ARE | | IN COMPLIANCE W/FLA.DEPT.OF HEALTH | | CHAPT.64E-9.OO6(F) FOR THE OCCUPANT | | LOAD OF THE POOL AND SPA ONLY! ANY | | OTHER USE SUCH AS WEDDINGS,PARTIES,ETC. | | CONSTITUTES A VIOLATION OF THE STD.PLBG. | | CODE SEC.407.1.3.FOR NUMBER OF MINIMUM | | REQUIRED SANITARY FACILITIES. |
|