Plan Review Notes
Plan Review Notes For Permit 99121640
Permit Number 99121640
Review Stop ENG
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00 
 SHEET C-2, NEED TO SHOW TWO LATERALS ON
 NARCISSUS, YOU ONLY SHOW ONE, AND BOTH
 NEED TO HAVE THE COMMENT "TO BE CUT AND
 PLUGGED AT THE MAIN BY THE CONTRACTOR".
  
 SHEET C-2, DOES NOT SHOW THE EXISTING 2"
 WATER SERVICE ON NARCISSUS AND THAT IT
 WILL BE REMOVED WHEN THE MAIN IS
 RELOCATED. INCLUDE THIS ON THE DRAWING
 AND THE STATEMENT "BY CONTRACTOR".
  
 SHEET C-1, THE EXFILTRATION TRENCH CAN
 NOT BE LOCATED IN THE SIDEWALK AREA OF
 NARCISSUS, THE STREET IS TOO NARROW AND
 THERE ARE TOO MANY UTILITIES IN THE
 AREA.THE AREA IS TO BE KEPT VACANT FOR
 FUTURE CITY UTILITIES.THIS WAS PART OF
 THE UTILITIES DEPARTMENT DISCUSSIONS
 WITH THE LAW DEPARTMENT TO ALLOW THIS
 BUILDING IN THE ROW OF NARCISSUS.
 RELOCATE THE EXFILTRATION TRENCH TO
 DATURA, UNDER THE SIDEWALK OR PAVED
 PARKING AREA. SUBMIT DOCUMENTS FOR AN
 EASEMENT ALSO SINCE THIS IS A PRIVATE
 STORMWATER SYSTEM IN THE CITY ROW.A
 SEPARATE EASEMENT WILL BE REQUIRED FROM
 THE PROPERTY OWNER, WITH A STATEMENT
 THAT THE PROPERTY OWNER WILL MAINTAIN
 THE SYSTEM.
  
 ADDITIONAL STORM WATER REQUIREMENTS:
 TO OBTAIN A CONSTRUCTION PERMIT THE
 FOLLOWING MUST BE SUBMITTED SIGNED AND
 SEALED BY A FLORIDA PROFESSIONAL
 ENGINEER (PE).
  
 CONSTRUCTION PLANS (SUPPLIED).
 DETAILS AND SPECIFICATIONS (SUPPLIED)
 HYDRAULIC COMPUTATIONS AND SUPPORTING
 DOCUMENTATION (NOT SUPPLIED)
 IMPERVIOUS AREA COMPUTATIONS (NOT
 SUPPLIED)
 POLLUTION PREVENTION PLAN (NOT
 SUPPLIED).THE POLLUTION PREVENTION
 PLAN SHALL BE KEPT ON SITE AT ALL TIMES
 DURING CONSTRUCTION. THE PLAN SHALL BE
 INSTALLED IN THE FIELD PRIOR TO ANY
 EARTHWORK. THE ENGINEER OF RECORD SHALL
 CERTIFY TO THE CITY, ON A MONTHLY BASIS,
 THAT THE PLAN IS WORKING PROPERLY AND AS
 DESIGNED. THE ENGINEER OF RECORD IS
 RESPONSIBLE TO CERTIFY IMPLEMENTATION OF
 THE PROVISIONS OF CITY ORDINANCE NO.
 3132-98 OF THE CITY CODE AT SUCH TIME
 THE PERMITTEE APPLIES FOR A CERTIFICATE
 OF OCCUPANCY FROM THE CITY BUILDING
 OFFICIAL
  
 EVERY SIX MONTHS AFTER CONSTRUCTION A PE
 SHALL CERTIFY THAT THE PERMANENT
 POLLUTION PREVENTION STRUCTURES, DRY-WET
 WATER DETENTION FACILITIES, AND
 EXFILTRATION SYSTEMS ARE WORKING AS
 DESIGNED AND ARE IN GOOD OPERATING
 CONDITION. ALL CERTIFICATIONS MUST BE
 SUBMITTED TO:
 STORM WATER UTILITY ENGINEER
 CITY OF WEST PALM BEACH PUBLIC UTILITIES
 DEPARTMENT
 P.O. BOX 3366, WEST PALM BEACH, FL
 33402.
 THE CERTIFICATION MUST INCLUDE THE
 BUILDING PERMIT NUMBER, THE ADDRESS OF
 THE PROPERTY AND THE NAME OF THE
 ESTABLISHMENT/PROJECT CONSTRUCTED.
  
 C-1 THE DROP CURB IS NOT ALLOWED AS
 DRAWN, THE CURB MUST PASS THROUGH THE
 FLAT AREA.
  
 THE PAVEMENT CAN HAVE A "V" NOTCH IN IT
 AS DRAWN PER RICHARD PITTMAN.BUT YOU
 NEED TO ADD THE COMMENT "SAW CUT AND
 MILL A MINIMUM OF 1" AT EDGE OF
 OVERLAY".
  
 PRIOR TO ANY OF THIS BEING ACCEPTED BY
 CITY ENGINEERING THE DESIGN ENGINEER
 MUST SHOW A 3 DIMENSIONAL DRAWING WITH
 EXISTING AND PROPOSED ELEVATIONS OF THE
 SIDEWALK AND PAVED AREA ON DATURA THAT
 WILL BE EFFECTED.THE ENGINEERING
 DIVISION WILL NOT APPROVE IT AS DRAWN
 SINCE THE PROPERTY WILL APPARENTLY FLOOD
 WITH ONLY ONE TENTH OF A FOOT DROP FROM
 THE FLOOR ELEVATION AND THE STREET.AN
 INTERNAL RAMP DOWN MAY BE THE ONLY
 ANSWER.
 SEE ENG 3 FOR MORE