2001-01-08 00:00:00 | PG.E101 SHOW ALL WORK NOTE #1 STATES TO | | TO INSTALL LIGHTS AND EMERGENCY | | PACKS, AND SWITCHES AT DOORS!!! | | SHOW THIS WORK ON DRAWINGS AND | | ALSO THE BRANCH CIRCUIT #S FOR | | THIS EQUIPMENT! | | | | PG.402ALL LOAD CALCULATIONS COME FROM | | 220.CITY NEEDS TO KNOW WHERE | | DEMANDS OF 66%, 70% ECT. ECT | | COME FROM?I AM HAVING TROUBLE | | FINDING THE SPECIFIC CODE | | SECTIONS WHICH ALLOWS THESE | | DEMANDS.FUTURE TENNANTS SHOW | | 70KW WITH A 70% DEMAND HOW WAS | | THIS DONE WHICH SPECIFIC CODE | | SECTION ALLOWS THIS!!!!!!!!!!! | | SUBMIT A LOAD CALC FOR THE SERVI | | THAT MEETS CODE SHOW CODE SECTIO | | FROM WHICH DEMANDS ARE TAKEN | | FROM! |
|