Plan Review Notes
Plan Review Notes For Permit 99121640
Permit Number 99121640
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00CORRECTED BY REVISION******************
  
 1)SHT LS1.1 NOTE XL EMERGENCY SERVICES
 NOTE D- DUCT SMOKE DETECTOR ALSO REQUIRE
 FOR UNITS LESS THAN 2000 CFM BUT SERVING
 AREAS USED FOR EGRESS-PER 1997 SMC 406.2
 ALSO REFERENCED SHT M-0.02 NOTE 16
 2)SHT M-2.1 OUTSIDE AIR INTAKE DUCT (24X
 8) REQUIRES FIRE DAMPER @ RATED WALL
 PENETRATION 2 PLACES
 3)SHT M-2.1 OUTSIDE AIR INTO TRANSFORMER
 VAULT PENETRATES RATED (4 HR) WALL,
 REQUIRES FIRE DAMPER OF EQUAL RATING
 EXHAUST FAN PENETRATES SAME 4 HR WALL
 PROVIDE DETAIL ON OPENING PROTECTIVES
 PER 1997 SMC 610.6
 4) SHT M-2.2 EXHAUST FANS TERMINATE IN
 TOILET COMPARTMENT, PROVIDE EXHAUST AIR
 TO ROOM WITH SHOWER/ TUB
 5) EXHAUST DUCTS PENETRATING RATED WALL
 REQUIRE PROTECTION PER 1997 SMC 610.1
 PROVIDE DETAILS
 6)SHT M-2.5 PROVIDE DETAIL FOR LEVEL 1
 MACHINE ROOM COMPLIANCE FOR MECHANICAL
 ROOM WITH CHILLER
 7)SHT M-4.1 OVERFLOW PROTECTION REQUIRED
 PER 1997 SMC 304.8.6
 8) PROVIDE DETAIL ON TERMINATION OF COND
 ENSATE DRAIN LINE AND DRAINLINE SIZES
 AND VENTING OF STACK