Notes
Date Text
2001-01-08 00:00:001- E300 NO WIRE SIZES SHOWN ON RISER
 DIAGRAM
  
 2- E300 NO LOAD CALCULATION SHOWN
  
 3- E401 PLEASE SHOW CODE ARTICLES USED
 TO SIZE PANELS.THE DEMANDS SHOWN
 COME FROM WHICH SECTION OF THE CODE?
  
 4- SEE SECTION 215-5 FOR THE REQUIREMENT
 FOR SIZING A SERVICE!!SHOW SQ.FT.
 ALL LOADS THAT WILL BE ATTACHED ECT.
 ECT.THEN YOU CAN SPLIT IT INTO TWO
 MAINS AND SO FORTH!LOAD CALC SHALL
 MEET THE MINIMUM CODE REQUIREMENTS!!!
  
 5- NO CONTINUOUS LOAD FACTOR SHOWN!!!!!
  
 6- NO AIC RATINGS SHOWN! 1109,10
  
 7- ROOF SHOWS POOL EQUIPMENT ROOM BUT
 NO PANEL OR EQUIPMENT????????
  
 8- E300 SHOWS A SECOND SERVICE WHAT
 WOUL;D THIS BE FEEDING?????????
 DOES IT MEET THE REQUIREMENTS OF
 230-2