Date |
Text |
2002-05-21 00:00:00 | METAL FRAMING SHOP DRAWINGS, | | CALCULATIONS BY THOMAS KELLEHER PE. | | THE CALCULATIONS CITE ASCE 7-93.THE | | 1997 SBCCI INVOKED THE ASCE 7-95. | | PLEASE REVISE AS NECESSARY. | | | | PROVIDE A METAL FRAMING DETAIL FOR THE | | CANOPY THAT THE " TITAN ROOFING" PANELS | | WILL BE ATTACHED TO. | | | | THE FIRE PROTECTION SYSTEM FOR THE | | CANOPY IS A COLUMN DESIGN.HOW ARE THE | | HORIZONTAL STRUCTURAL MEMBERS PROTECTED? |
|