Plan Review Notes For Permit 99121621
Permit Number 99121621
Review Stop B
Sequence Number 9
Notes
Date Text
2002-05-21 00:00:00METAL FRAMING SHOP DRAWINGS,
 CALCULATIONS BY THOMAS KELLEHER PE.
 THE CALCULATIONS CITE ASCE 7-93.THE
 1997 SBCCI INVOKED THE ASCE 7-95.
 PLEASE REVISE AS NECESSARY.
  
 PROVIDE A METAL FRAMING DETAIL FOR THE
 CANOPY THAT THE " TITAN ROOFING" PANELS
 WILL BE ATTACHED TO.
  
 THE FIRE PROTECTION SYSTEM FOR THE
 CANOPY IS A COLUMN DESIGN.HOW ARE THE
 HORIZONTAL STRUCTURAL MEMBERS PROTECTED?