2002-05-10 00:00:00REVISIONS SUBMITTED 5/1/02
 SHEET A110 REVISIONS NUMBERED 1-8.THE
 PERMIT PLANS HAVE REV 1, SOME OF THE
 REVISONS ARE DATED TWO YEARS AGO, WHY
 ARE THEY JUST NOW BEING PROVIDED TO THE
 CITY FOR REVIEW?
  
 PROVIDE DETAILS FOR THE BUILT IN BAR
 SHOWN INCLUDING HC ACCESIBILITY
 REQUIREMENTS.
  
 THE PLANS HAVE REFERENCE SECTIONS TO
 A802.THE PERMIT PLANS DO NOT SHOW
 SECTION DETAILS NUMBERED THAT HIGH,
 THEYSTOP AT DETAIL 6, THESE PLANS SHOW
 17.
  
 SHEET A111.PROVIDE A CONSTRUCTION
 DETAIL FOR THE SUSPENDED CEILING.
 REVISIONS SHOWN 1-6, PERMIT PLANS 0.
  
 SHEET A120 REVISIONS 1-6, PERMIT PLAN 0.
 THE HANDRAILS FOR THE STAIRS FROM THE
 POOL DECK TO THE CLUBHOUSE DO NOT
 COMPLY WITH THE 30" REACH RANGE OF SBC
 1007.5.7.THE STAIRS AT THE FOUNTAIN
 AREA REQUIRE HANDRAILS ON BOTH SIDES
 AND THE RANGE OF REACH REQUIREMENTS OF
 SBC 1007.5.2ANDSBC 1007.5.7.
  
 SHEET A201 REV 1-8, PERMIT SET 1-4.
 PROVIDE STRUCTURAL DETAILS FOR THE
 CANOPY.THIS WAS REQUESTED ON MY
 CHECKLIST DATED 4/18/02 DENYING THOSE
 REVISIONS.
  
 WHAT PERMITTED PLAN DID THE THRESHOLD
 INSPECTOR USE TO INSPECT THIS
 STRUCTURAL WORK?
  
 SHEET A323 REVISIONS 1-3, PERMIT SET 1.
 PROVIDE A CONSTRUCTION DETAIL FOR THE
 ADDED MASONRY VEHICLE BARRIER WALL
 INCLUDING CALCULATIONS DEMONSTRATING
 COMPLIANCE WITH THE LOADS PRESCRIBED IN
 SBC 1608.2.3.
  
 SHEET A404 REVISIONS 1-4, PERMIT SET 0.
 PROVIDE A DETAIL FOR CONSTRUCTION OF
 THEADDED VAULT.
  
 SHEET A406 REVISIONS 1-5, PERMIT SET 0.
 PROVIDE DETAILS FOR THE GALVANIZED
 SHUTTER.WHAT IS IT FOR?THE 4" HIGH
 CURBS AT THE PATIO SLIDING DOORS DO NOT
 COMPLY WITH THE FAIR HOUSING ACT.SEE
 PART 2, CHAPTER 4, PAGE 4.11 OF THE FHA
 DESIGN MANUAL.
  
 SHEET A421 REVISIONS 1-3, PERMIT SET 0.
 PROVIDE A DETAIL OF WHAT THE ADDED
 WALKWAY WILL BE MADE OF.
  
 SHEET A425 REVISIONS 1-3, PERMIT SET 0.
 SECTION DETAILS REFERENCED AS"XX/804"
 ARE ABSENT FROM THE PERMIT PLANS.
  
 SHEET E1.06, PROVIDE INFORMATION FOR THE
 METHOD OF OPENING PROTECTIVE FOR THE
 ADDED EXHAUST FAN.SEE SBC TABLE 600.