2002-05-10 00:00:00 | REVISIONS SUBMITTED 5/1/02 |
| SHEET A110 REVISIONS NUMBERED 1-8.THE |
| PERMIT PLANS HAVE REV 1, SOME OF THE |
| REVISONS ARE DATED TWO YEARS AGO, WHY |
| ARE THEY JUST NOW BEING PROVIDED TO THE |
| CITY FOR REVIEW? |
| |
| PROVIDE DETAILS FOR THE BUILT IN BAR |
| SHOWN INCLUDING HC ACCESIBILITY |
| REQUIREMENTS. |
| |
| THE PLANS HAVE REFERENCE SECTIONS TO |
| A802.THE PERMIT PLANS DO NOT SHOW |
| SECTION DETAILS NUMBERED THAT HIGH, |
| THEYSTOP AT DETAIL 6, THESE PLANS SHOW |
| 17. |
| |
| SHEET A111.PROVIDE A CONSTRUCTION |
| DETAIL FOR THE SUSPENDED CEILING. |
| REVISIONS SHOWN 1-6, PERMIT PLANS 0. |
| |
| SHEET A120 REVISIONS 1-6, PERMIT PLAN 0. |
| THE HANDRAILS FOR THE STAIRS FROM THE |
| POOL DECK TO THE CLUBHOUSE DO NOT |
| COMPLY WITH THE 30" REACH RANGE OF SBC |
| 1007.5.7.THE STAIRS AT THE FOUNTAIN |
| AREA REQUIRE HANDRAILS ON BOTH SIDES |
| AND THE RANGE OF REACH REQUIREMENTS OF |
| SBC 1007.5.2ANDSBC 1007.5.7. |
| |
| SHEET A201 REV 1-8, PERMIT SET 1-4. |
| PROVIDE STRUCTURAL DETAILS FOR THE |
| CANOPY.THIS WAS REQUESTED ON MY |
| CHECKLIST DATED 4/18/02 DENYING THOSE |
| REVISIONS. |
| |
| WHAT PERMITTED PLAN DID THE THRESHOLD |
| INSPECTOR USE TO INSPECT THIS |
| STRUCTURAL WORK? |
| |
| SHEET A323 REVISIONS 1-3, PERMIT SET 1. |
| PROVIDE A CONSTRUCTION DETAIL FOR THE |
| ADDED MASONRY VEHICLE BARRIER WALL |
| INCLUDING CALCULATIONS DEMONSTRATING |
| COMPLIANCE WITH THE LOADS PRESCRIBED IN |
| SBC 1608.2.3. |
| |
| SHEET A404 REVISIONS 1-4, PERMIT SET 0. |
| PROVIDE A DETAIL FOR CONSTRUCTION OF |
| THEADDED VAULT. |
| |
| SHEET A406 REVISIONS 1-5, PERMIT SET 0. |
| PROVIDE DETAILS FOR THE GALVANIZED |
| SHUTTER.WHAT IS IT FOR?THE 4" HIGH |
| CURBS AT THE PATIO SLIDING DOORS DO NOT |
| COMPLY WITH THE FAIR HOUSING ACT.SEE |
| PART 2, CHAPTER 4, PAGE 4.11 OF THE FHA |
| DESIGN MANUAL. |
| |
| SHEET A421 REVISIONS 1-3, PERMIT SET 0. |
| PROVIDE A DETAIL OF WHAT THE ADDED |
| WALKWAY WILL BE MADE OF. |
| |
| SHEET A425 REVISIONS 1-3, PERMIT SET 0. |
| SECTION DETAILS REFERENCED AS"XX/804" |
| ARE ABSENT FROM THE PERMIT PLANS. |
| |
| SHEET E1.06, PROVIDE INFORMATION FOR THE |
| METHOD OF OPENING PROTECTIVE FOR THE |
| ADDED EXHAUST FAN.SEE SBC TABLE 600. |