2002-03-26 00:00:00REVISIONS SUBMITTED 2/28/02 HAVING
 VARIOUS DATES ON THE PLANS AND REVISION
 DELTAS 1 THROUGH 7.ARCH. PAGES
  
 SHEET A 101. PROVIDE STRUCTURAL DETAILS
 FOR THE ADDED LOUVERS PENETRATING THE
 EXTERIOR WALLS.SBC 104.2
  
 SHEET A 202. PROVIDE STRUCTURAL DETAILS
 FOR THE REVISED ENTRY.
  
 SHEET A 206.PROVIDE STRUCTURAL DETAILS
 FOR THE ADDED MECHANICAL EQUIPMENT
 ADDRESSING THE CONCENTRATED LOADINGS
 AND NEW PENETRATION/OPENINGS.
  
 SHEET A 303.STRUCTURAL INFORMATION FOR
 THE ADDED COOLING TOWER ENCLOSURE, AND
 THE CURB SHOWN IN SECTION 6/A303.
  
 A 310 PROVIDE STRUCTURAL DETAILS FOR THE
 SUSPENDED CEILING FRAMING INCLUDING
 CONNECTION TO THE SLAB ABOVE.
  
 A 320.STRUCTURAL DETAILS FOR THE NEW
 ARCH FRAMING.
  
 A 323 AND A 425.PROVIDE STRUCTURAL
 DETAILS FOR THE ADDED CANOPY.ALSO IT
 DOES NOT APPEAR TO COMPLY WITH SBC
 3204.3.
 REVISE AS NECESSARY.
  
 SHEET A 406 AND SEVERAL SUBSEQUENT PAGES
 INDICATE A 4" HIGH CURB AT THE PATIO
 SGD.THIS DOES NOT COMPLY WITH THE
 FAIR HOUSING MANUAL GUIDELINES PAGE
 4.11PLEASE REVISE AS NECESSARY.
  
 SHEET ADD 1.PROVIDE THE FIRE DESIGN
 NUMBERS FOR THE PRIMARY AIRSHAFT WALLS.
 SEE SBC 701.5.