2002-03-26 00:00:00 | REVISIONS SUBMITTED 2/28/02 HAVING |
| VARIOUS DATES ON THE PLANS AND REVISION |
| DELTAS 1 THROUGH 7.ARCH. PAGES |
| |
| SHEET A 101. PROVIDE STRUCTURAL DETAILS |
| FOR THE ADDED LOUVERS PENETRATING THE |
| EXTERIOR WALLS.SBC 104.2 |
| |
| SHEET A 202. PROVIDE STRUCTURAL DETAILS |
| FOR THE REVISED ENTRY. |
| |
| SHEET A 206.PROVIDE STRUCTURAL DETAILS |
| FOR THE ADDED MECHANICAL EQUIPMENT |
| ADDRESSING THE CONCENTRATED LOADINGS |
| AND NEW PENETRATION/OPENINGS. |
| |
| SHEET A 303.STRUCTURAL INFORMATION FOR |
| THE ADDED COOLING TOWER ENCLOSURE, AND |
| THE CURB SHOWN IN SECTION 6/A303. |
| |
| A 310 PROVIDE STRUCTURAL DETAILS FOR THE |
| SUSPENDED CEILING FRAMING INCLUDING |
| CONNECTION TO THE SLAB ABOVE. |
| |
| A 320.STRUCTURAL DETAILS FOR THE NEW |
| ARCH FRAMING. |
| |
| A 323 AND A 425.PROVIDE STRUCTURAL |
| DETAILS FOR THE ADDED CANOPY.ALSO IT |
| DOES NOT APPEAR TO COMPLY WITH SBC |
| 3204.3. |
| REVISE AS NECESSARY. |
| |
| SHEET A 406 AND SEVERAL SUBSEQUENT PAGES |
| INDICATE A 4" HIGH CURB AT THE PATIO |
| SGD.THIS DOES NOT COMPLY WITH THE |
| FAIR HOUSING MANUAL GUIDELINES PAGE |
| 4.11PLEASE REVISE AS NECESSARY. |
| |
| SHEET ADD 1.PROVIDE THE FIRE DESIGN |
| NUMBERS FOR THE PRIMARY AIRSHAFT WALLS. |
| SEE SBC 701.5. |