2001-01-08 00:00:00******************PROVISO***************
 1)SHT.A-601-BACKING FOR GRAB BARS FOR
 THE TUB ALONG THE LONG WALL SHALL COMPLY
 W/THE FHA REQ.#6,FIG.4.THE PLANS SHOW 8"
 MAX.TO THE BOTTOM OF THE BACKING AND THE
 FHA REQ.IS 6".
  
 2)SHT.A-453-UNIT D9-THE WATER CLOSET
 INFRINGES ON THE CLEAR FLOOR SPACE IN
 THE M.B.TOILET ROOM.COMPLY W/FHA 24 CFR
 100.205(C)(3)(IV).
  
 3)SHTS.A-120,A204,A414 SHOW 1 TOILET
 ROOM IN THE POOL CLUBHOUSE AND SHT.A110
 SHOWS 2 TOILET ROOMS.PLEASE REVISE SO
 ALL APPLICABLE SHEETS CORRELATE.
  
 4)SHT.A-601-A MIN. OF 29"IS REQD.UNDER
 LAV.FROMM FINISH FLOOR TO BOTTOM OF
 APRON,NOT 27".COMPLU W/FACBC SEC.4.19.
  
 5)A DRINKING FOUNTAIN IS REQD.INSIDE THE
 CLUBHOUSE PER TABLE 407.DRINKING
 FOUNTAIN IS REQD.IN THE CLUBHOUSE PER
 TABLE 407.FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BEND-
 ING OR STOOPING.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
  