Plan Review Notes For Permit 99121621 |
Permit Number |
99121621 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1. PROVIDE DOOR SCHEDULE | | 2. FIRE ALARM SYSTEM SHALL BE CLASS "A" | | OR ADDRESSABLE. | | 3. PROVIDE ADDITIONAL STANDPIPE. | | 4. ALL EXIT DOORS SHALL SWING IN THE | | DIRECTION OF EXIT TRAVEL. | | 5. PROVIDE 2 1/2"TO 1 1/2" REDUCERS ON | | ALL STANDPIPES. | | 6.ALL APT. DOORS SHALL BE 20 MIN., SELF | | CLOSING, FIRE DOORS. | | 7. ALL INTERIOR STAIRWELL DOORS SHALL | | BE CLASS B RATED, SELF CLOSING, FIRE | | DOORS. | | 8. PROVIDE FIRE SPRINKLER DRAWINGS. |
|