Plan Review Notes
Plan Review Notes For Permit 99121621
Permit Number 99121621
Review Stop FIRE
Sequence Number 13
Notes
Date Text
2002-07-18 00:00:001) PLEASE SUBMIT A COMPREHENSIVE
 NARRATIVE FOR THE SMOKE CONTROL SYSTEM
 PLANNED FOR USE. THE ORIGINAL DESIGN
 INDICATED PRESSURIZING TWO FLOORS ABOVE
 AND TWO FLOORS BELOW WITH THE FLOOR
 OF INCIDENT BETWEEN THESE. DURING
 TESTING WITH CITY MECHANICAL DIVISION
 PERSONNEL, PROBLEMS WERE IDENTIFIED
 AND THUS THE ORGINAL DESIGN HAS SINCE
 BEEN CHANGES. THE NARRATIVE IS
 REQUIRED FROM THE ENGINEER OF RECORD
 TO PROVIDE SUPPORTIVE DOCUMENTATION
 FOR THE DESIGN CHANGE.
  
 2) IS IS UNDERSTOOD BY THIS OFFICE THAT
 A TEMPROARY SHROUD HAS BEEN INSTALLED
 ON THE FAN. THIS TEMPORARY DEVICE IS
 TO BE REMOVED AS IT NOT PART OF THE
 ORIGINAL LISTING FOR THE FAN DEVICE.
  
 3) THE ACCEPTANCE TESTING CRITERIA
 NOTED ON THE PLANS ARE TO BE FOLLOWED.
  
 4) THE OWNER, ENGINEER, AND CONTRACTOR
 MUST ACCEPT THE LIABILTIY FOR
 THE PRESCRIBED SYSTEM DURING TESTING
 SINCE THE DESIGN INTENT HAS CHANGED
 SIGNIFICANTLY. THE ENGINEER OF RECORD
 SHALL BE CONSULTED DURING THE ENTIRE
 TESTING PROCESS.
  
 5) THE FUNCTIONAL APPROVAL BY CITY
 OFFICIALS WILL ONLY OCCUR AFTER
 MUTUALLY AGREED UPON TESTING METHODS
 AND RESULTS ARE DISCUSSSED.
  
 6) ALL APPLICABLE BUILDING, FIRE , AND
 MECHANICAL CODES ARE TO BE MET FOR
 THE SYSTEM WITHIN THE BUILDING.