2002-06-03 00:00:00DENIED
 REFERENCE: SPC-94- FACBC-97
  
 1) SHT A110 SHOW DETAIL FOR WATER HEATER
 SHOW HOW IT WILL BE READILY ACCESSIBLE.
 SHOW PIPING FOR T/P RELIEF LINE AND FOR
 PAN DRAIN.
 2) SHT A110 DOOR SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE OF ANY HDCP FIXT-
 URE. SEC 4.22.2
 3) SHT P126 PLEASE SUBMIT FACTORY INFO.
 FOR MISTING MACHINE. SHOW LISTING FOR
 PRODUCT APPROVAL.
 4) SK-P-1/SK-P-2 RISER DIAGRAMS, HUB
 DRAINS NOT APPROVED. FLOOR SINK REQUIRED
 FOR ALL INDIRECT WASTE. SEC 804.5
 5) SHT A110 PLEASE PROVIDE CHANGE IN
 SANT RISER DIAGRAM FOR NEW SINK IN CLUB
 ROOM
  