Plan Review Notes
Plan Review Notes For Permit 99121621
Permit Number 99121621
Review Stop E
Sequence Number 10
Notes
Date Text
2002-05-30 00:00:00************** UNSAT *************
  
 1)NOTE: PLEASE CLARIFY REVISIONS SHOWN
 FOR SOME PANELS ON RISER DIAGRAM AND
 NOTES REF "SEE PANEL SCHEDULES". PLEASE
 NOTE NO PANEL SCHEDULES WERE SUBMITTED
 FOR THOSE MENTIONED. NOTE REF CHANGE TO
 FEEDERS TO APTS ALSO.?METER CENTERS ALSO
  
 2)NOTE: PLEASE NOTE THAT SINCE THIS
 REV WAS SUBMITTED, THE RISER DIAGRAM
 HAS CHANGED DUE TO FIELD EVALUATION OF
 MAIN DISC`S AND/OR GROUPING OF MAINS.
 PLEASE REVISE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372