2001-01-08 00:00:00***********NOT ENOUGH INFORMATION******
  
 INSUFFICIENT MECHANICAL INFORMATION TO
 REVIEW:
 PROVIDE DETAILS AT TIME OF SUBMITION FOR
 BUILDING REVIEW. INCLUDE:
 EQUIPMENT TYPES AND LOCATION
 REFRIGERANT TYPE AND QUANTITY PER 1997
 SMC CHAPTER 11
 DUCT LAYOUT, SIZES AND SPECIFICATIONS
 FAN SHUT DOWN PER 1997 SMC 406,NFPA90A,
 AND 1997 SBC 412.2
 SMOKE CONTROL PER 1997 SBC 412.5
 STAIRWELL PRESSURIZATION PER 1997 SMC
 408 AND NFPA 92A
 INCLUDE SEQUENCE OF OPERATION FOR SMOKE
 CONTROL AND FAN SHUT DOWN SYSTEMS
 SHAFT ENCLOSURE DETAILS FOR EXHAUST DUCT
 FOR HOOD AND MAKE UP AIR LOCATION FOR
 HOOD
 OUTSIDE AIR CALCULATIONS AND AIR BALANCE
 SCHEDULE PER ASHRAE 62-89 AND SMC 501.2
  
  
 NOTE:SMC=STANDARD MECHANICAL CODE
 SBC=STANDARD BUILDING CODE
 NFPA=NATIONAL FIRE PROTECTION ASSOCIA-
 TION