2001-01-08 00:00:00************** PROVISO *****************
  
 1)NOTE:PLEASE REVISE SHEET E1.1 TO
 REFLECT WIRE SIZE FOR SITE LIGHTING AS
 REQ`D ON SHEET E5.1.
  
 2)NOTE:AS REQ`D BY ARTS;250-81/250-94
 OF THE NEC. THE BONDING JUMPER/GROUNDING
 ELECTRODE CONDUCTOR GOING TO COLD WATER
 PIPEIS REQ`D BY 250-81 TO BE SIZED
 FROM 250-94. PLEASE CORRECT.
  
 3)NOTE: THERE IS TO BE NO EQUIUPMENT
 GROUNDING CONDUCTOR INSTALLLED UNTIL
 AFTER FIRST MEANS OF DISCONNECT.
  
  
 PLEASE HAVE THE ABOVE SUBMITTED FOR RE-
 -VIEW AND APPROVAL BEFORE FIRST ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372