Plan Review Notes
Plan Review Notes For Permit 99121523
Permit Number 99121523
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SHT.P-1-THE WATER SERVICE TO THE CABANA
 REQUIRES A BACKFLOW PREVENTION DEVICE.
 SPC SEC.606.1.
  
 THE DRINKING FOUNTAIN AT THE CABANA
 SHALL COMPLY W/FACBC SEC.4.1.3(10)(A)
 AND BE ON AN ACCESSIBLE ROUTE PER FACBC
 SEC.4.3.1.
  
 CLEARLY SHOW DIMENSIONS OF TOILET ROOMS.
 COMPLY W/FACBC SEC.4.16.2 AND FIG.28.
  
 SUBMIT COMPLETE POOL PLANS TO ENSURE
 COMPLIANCE W/DEPT.OF HEALTH CHAPT.64E-9.
 POOL PLANS SHALL BE REVIEWED AND
 APPROVED BY HEALTH DEPT.PRIOR TO REVIEW
 BY THIS DEPT.COUNTYWIDE AMENDMENTS TO
 SPC SEC.101.4.7.
  
 SUBMIT DETAILS FOR HANDICAP FIXTURES.
 (MOUNTING HEIGHTS,CLEAR FLOOR SPACE AT
 FIXTURES,ETC.).
  
 FLOOR AND WALLS IN CABANA SHALL BE
 NONABSORBENT TO A HEIGHT OF 4'PER SBC
 SEC.1204.2.
  
 POOL SHOWER SHALL COMPLY W/FACBC 4.21.6
 (EXCEPTION)AND BE ON AN ACCESSIBLE
 ROUTE PER FACBC SEC.4.3.1.
  
 SHUTOFF VALVE REQD.ON WATER SERVICE PER
 SPC 610.1.AND WATER SUPPLY CONTROL FOR
 CABANA SHALL COMPLY W/SPC SEC.610.4.1,
 610.4.2.
  
 DELETE OR VOID BLUEPRINTS NOT APPLICABLE
 TO THIS PERMIT.COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1.
  
 SEPARATE PERMIT REQD.FOR FOUNTAIN.COUNTY
 WIDE AMENDMENTS TO SPC SEC.104.1.1.