Plan Review Notes
Plan Review Notes For Permit 99121523
Permit Number 99121523
Review Stop B
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001. PRODUCT APPROVALS FOR ROOFING AND
 DOORS NOT SUBMITTED.
 2. TRUSS DRAWINGS NOT SUBMITTED.
 3. SHEET A-1 INDICATES BUILDING TYPE VI
 CONSTRUCTION SEE 1997 SBC APPENDIX F FOR
 BUILDINGS LOCATED IN FIRST FIRE DISTRICT
 BUILDING MUST BE TYPE V ONE HOUR CONST.
 4. SHEET A-38 ENTRANCE FROM SERVICE
 ALLEY NOT HANDICAPPED ACCESSABLE.
 REQUIRED AS THIOS IS THE ONLY OFF SITE
 ACCESS POINT TO POOL CABANA AREA.
 5. SHEET A-38 HEALTH DEPARTMENT TO
 REVIEW AND APPROVE PLANS.
 6. SHEET A-38 POOL EQUIPMENT BUILDING
 SHALL BE SIZED TO MEET ALL CLEARANCE
 REQUIREMENTS FOR EQUIPMENT INSTALLED.
 7. SHEET A-38 POOL, FOUNTIAN, WALLS AND
 FENCES REQUIRE SEPERATE PERMITS.
 8. SHEET A-38 POOL GATE LATCH SHALL
 COMPLY WITH CITY OF WEST PALM BEACH
 POOL CODE SECTION 42.
 9. SHEET A-39 PROVIDE SPECIAL INSPECTOR
 AS PER PLAN NOTES.
 10. ROOF NOTES, DESIGN IS TO ASCE 7-93,
 1997 SBC REQUIRES DESIGN TO COMPLY WITH
 ASCE 7-95.