Plan Review Notes
Plan Review Notes For Permit 99121451
Permit Number 99121451
Review Stop R
Sequence Number 2
Notes
Date Text
2001-04-19 00:00:00DENIED
  
 1) TYPICAL EXTERIOR CEILING DETAIL ON
 SHEET A-2 IS INCORRECT; SEE 1997 SBC
 SEC.2504.2.2 WHICH REFERS TO ASTM C 1603
 AT LEAST 1 3/4" PENETRATION INTO
 HORIZONTAL WOOD FRAMING MEMBER IS
 REQUIRED. PLEASE CORRECT.
  
 2) THE 2ND STORY LOFT WINDOW (RIGHT
 ELEVATION) EXCEEDS THE 20% OF OPENING
 AREA ALLOWED BY TABLE 600 OF 97 SBC.
 PLEASE CORRECT.
  
 3) THE BLOCK PRIVACY WALL IS SHOWN AT A
 HEIGHT OF 8' ON SHEETS A-2 & A-4. THE
 MAXIMUM HEIGHT ALLOWED IS 6'. PLEASE
 CORRECT. THIS WILL AFFECT TABLE 600.
  
 4) PROVIDE NEGATIVE AND POSITIVE DESIGN
 PRESSURES (PSF) FOR ALL EXTERIOR DOOR
 AND WINDOW OPENINGS.
  
 5) STRUCTURE IS LOCATED IN AN "A8" FLOOD
 ZONE. AN ELEVATION CERTIFICATE WILL BE
 REQUIRED PRIOR TO RECEIVING A C.O.
  
 6)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - FLAT ROOF SYSTEM
  
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202