2001-04-19 00:00:00 | DENIED | | | | 1) TYPICAL EXTERIOR CEILING DETAIL ON | | SHEET A-2 IS INCORRECT; SEE 1997 SBC | | SEC.2504.2.2 WHICH REFERS TO ASTM C 1603 | | AT LEAST 1 3/4" PENETRATION INTO | | HORIZONTAL WOOD FRAMING MEMBER IS | | REQUIRED. PLEASE CORRECT. | | | | 2) THE 2ND STORY LOFT WINDOW (RIGHT | | ELEVATION) EXCEEDS THE 20% OF OPENING | | AREA ALLOWED BY TABLE 600 OF 97 SBC. | | PLEASE CORRECT. | | | | 3) THE BLOCK PRIVACY WALL IS SHOWN AT A | | HEIGHT OF 8' ON SHEETS A-2 & A-4. THE | | MAXIMUM HEIGHT ALLOWED IS 6'. PLEASE | | CORRECT. THIS WILL AFFECT TABLE 600. | | | | 4) PROVIDE NEGATIVE AND POSITIVE DESIGN | | PRESSURES (PSF) FOR ALL EXTERIOR DOOR | | AND WINDOW OPENINGS. | | | | 5) STRUCTURE IS LOCATED IN AN "A8" FLOOD | | ZONE. AN ELEVATION CERTIFICATE WILL BE | | REQUIRED PRIOR TO RECEIVING A C.O. | | | | 6)PROVIDE (2) CURRENT AND COMPLETE | | COPIES OF SBCCI OR METRO-DADE PRODUCT | | APPROVALS FOR: | | - FLAT ROOF SYSTEM | | | | | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)659-8096 EXT.8202 |
|