2001-01-08 00:00:00SIZE THE PLUMBING RISER IN ITS ENTIRETY
 PER COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 ALL FIXTURES DOWMSTREAM OF WATER CLOSETS
 SHALL BE INDIVIDUALLY VENTED PER SPC
 913.2.AND SHOWERS SHALL BE TRAPPED.
  
 SHOW DIMENSIONS OF 2ND FLR.SHOWER.(LXW)
 COMPLY W/COUNTYWIDE AMENDMENTS TO SPC
 SEC.409.8.2.1.
  
 THE LOCATION OF PLUMBING FIXTURES ON THE
 PLUMBING RISER SHALL MATCH THE ARCH.
 FLOOR PLAN. COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 MAIN VENT REQD.THRU ROOF.SPC SEC.904.3.1
  
 BUILDING DRAIN SHALL COMPLY W/SPC SEC.
 714.1 & TABLE 714.1(FOOTNOTE #3.)
  
 CLARIFY TERMINATION POINT OF KIT.DRAIN.
 (PLANS SHOW OPEN PIPE.)
  
 WATER CLOSETS AND FIXTURE BRANCHES NOT
 PERMITTED ON HORIZONTAL WET VENTS PER
 COUNTYWIDE AMENDMENTS 911.1