Plan Review Notes For Permit 99121447 |
Permit Number |
99121447 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | 1)NOTE:NEED TO INCLUDE BLDG.STEEL AS | | PART OF THE GROUNDING ELECTRODE SYSTEM. | | AS REQ`D BY 250-81 | | | | 2)NOTE:NEED TO LIST ON PANEL SCEDULES | | THE DEDICATED BATH(S) CIRCUT(S) REQ`D | | BY 210-52D THEY MUST BE 20AMP #12 AWG. | | | | 3)NOTE: PLEASE DRAW ON PLANS BOTH DISC.S | | THAT ARE SHOWN ON RISER DIAGRAM. 215-5 | | | | 4)NOTE: AS NOTED BEFORE,, NEED TO SUBMIT | | THE AIC RATING OF ALL EQUIPMENT MAINS!!! | | MAINS MUST BE RATED FOR THE AVAILABLE | | FAULT CURRENT FIGURED FROM FAULT CURRENT | | CALCULATIONS. REQ`D BY 110-9/110-10 AND | | 215-5 OF THE NEC. | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | FOR REVIEW AND APPROVAL. IF THERE ARE | | ANY QUESTIONS PLEASE CALL 659-8096 | | EXT 8372 |
|