Plan Review Notes
Plan Review Notes For Permit 99121447
Permit Number 99121447
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE:NEED TO INCLUDE BLDG.STEEL AS
 PART OF THE GROUNDING ELECTRODE SYSTEM.
 AS REQ`D BY 250-81
  
 2)NOTE:NEED TO LIST ON PANEL SCEDULES
 THE DEDICATED BATH(S) CIRCUT(S) REQ`D
 BY 210-52D THEY MUST BE 20AMP #12 AWG.
  
 3)NOTE: PLEASE DRAW ON PLANS BOTH DISC.S
 THAT ARE SHOWN ON RISER DIAGRAM. 215-5
  
 4)NOTE: AS NOTED BEFORE,, NEED TO SUBMIT
 THE AIC RATING OF ALL EQUIPMENT MAINS!!!
 MAINS MUST BE RATED FOR THE AVAILABLE
 FAULT CURRENT FIGURED FROM FAULT CURRENT
 CALCULATIONS. REQ`D BY 110-9/110-10 AND
 215-5 OF THE NEC.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096
 EXT 8372