Plan Review Notes
Plan Review Notes For Permit 99121250
Permit Number 99121250
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00CORRECTED BY REVISIONS3/9/00**********
  
 1) SHT A-31 DETAIL 3 DRYER VENT AND BAT
 EXHAUST DUCT TO BE ENCLOSED IN SHAFT TO
 BOTTOM OF ROOF STRUCTURE
 2) SHT A-31 DETAIL 2 DRYER VENT TO BE
 MIN. 4" NOT 3", DRYER VENT TO RUN FULL
 LENGTH OUT OF BUILDING
 3) SHT A-31 DETAIL 4 INDICATE WHICH SIZE
 CAP TO BE USED- 4" OR 2 1/2" NOTE: FLEX
 METAL DUCT NOT ALLOWED BY CODE
 4) SHT AC-1 AREAS WITH 300CFM OR GREATER
 REQUIRES RETURN AIR FROM AREA
 5) SHT AC-1 PROVIDE MANUFACTURES SPEC'S
 ON CAPACITY TO PUSH LENGTH OF DUCT USED
 6) ANY DUCT PENETRATING RATED CEILING
 TO HAVE FIRE DAMPERS PER 1997 SMC 610.2
 7) CONDENSING UNIT SERVICE TO BE PER NE
 AND 1997 SMC 304.7.2 WHICHEVER IS GREAT
 ER. DISCONNECT TO BE WITHIN 6' OF THE
 SERVICE SIDE OF THE EQUIPMENT AND A 115
 GFIC OUTLET REQUIRED.
 8) SHT AC 5 OVERFLOW PROTECTION REQUIRE
 FOR AHU'S PER 1997 SMC 304.8.6
 9) BATHROOM EXHAUST DUCT SHOWN PENETRAT
 ING 2ND FL CONC. FLOOR SLAB ABOVE GARAG
 PROVIDE DETAIL TO SHOW COMPLIANCE W/ SM
 610.2 AND 610.4. SHAFT ENCLOSUREREQ'D
 FOR FIRE PROTECTION OF ASSEMBLY.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved