2001-01-08 00:00:00 | CORRECTED BY REVISIONS3/9/00***** |
| |
| 1) SHT A-31 DETAIL 3 DRYER VENT AND BATH |
| EXHAUST DUCT TO BE ENCLOSED IN SHAFT TO |
| BOTTOM OF ROOF STRUCTURE |
| 2) SHT A-31 DETAIL 2 DRYER VENT TO BE |
| MIN. 4" NOT 3", DRYER VENT TO RUN FULL |
| LENGTH OUT OF BUILDING |
| 3) SHT A-31 DETAIL 4 INDICATE WHICH SIZE |
| CAP TO BE USED- 4" OR 2 1/2" NOTE: FLEX |
| METAL DUCT NOT ALLOWED BY CODE |
| 4) SHT AC-1 AREAS WITH 300CFM OR GREATER |
| REQUIRES RETURN AIR FROM AREA |
| 5) SHT AC-1 PROVIDE MANUFACTURES SPEC'S |
| ON CAPACITY TO PUSH LENGTH OF DUCT USED |
| 6) ANY DUCT PENETRATING RATED CEILING |
| TO HAVE FIRE DAMPERS PER 1997 SMC 610.2 |
| 7) CONDENSING UNIT SERVICE TO BE PER NEC |
| AND 1997 SMC 304.7.2 WHICHEVER IS GREAT- |
| ER. DISCONNECT TO BE WITHIN 6' OF THE |
| SERVICE SIDE OF THE EQUIPMENT AND A 115V |
| GFIC OUTLET REQUIRED. |
| 8) SHT AC 5 OVERFLOW PROTECTION REQUIRED |
| FOR AHU'S PER 1997 SMC 304.8.6 |
| 9) BATHROOM EXHAUST DUCT SHOWN PENETRAT- |
| ING 2ND FL CONC. FLOOR SLAB ABOVE GARAGE |
| PROVIDE DETAIL TO SHOW COMPLIANCE W/ SMC |
| 610.2 AND 610.4. SHAFT ENCLOSUREREQ'D |
| FOR FIRE PROTECTION OF ASSEMBLY. |