2001-01-08 00:00:001-110-16 WORKING CLEARANCE AT METERS
 WILL BE 3' IN FRONT OF METER!!!!!
  
 2-MAIN FOR PANEL "HD" WILL HAVE TO BE
 GROUPED WITH METERS AND OTHER MAINS
 SHOWN AT THIS LOCATION.
  
 3-TYPE 2 TOWNHSE. WILL HAVE TO PUT A D
 DISCONNECT AT THE WATER HEATER
  
 3-NOT SURE ON TYPE 1 CAN'T TELL IF
 THERE IS A WALL IN FROINT OF THE
 WATER HEATER.
  
 4-NEED A RISER DIAGRAM SHOWING HOW
 PANEL HD IS TO BE FED ALONG WITH THE
 TOWNHSE. METER AND MAIN!!!!!!!!!!!!
  
 5-SUBMIT THIS INFORMATION BEFORE 1ST
 ELECTRICAL INSPECTION (ROUGH)