Plan Review Notes
Plan Review Notes For Permit 99121241
Permit Number 99121241
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00****************PLUMBING****************
 BUILDING 3D
 WATER RISER FOR UNIT "D" DOESN'T MATCH
 THE ARCH. FLOOR PLAN.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1.
  
 A PERMIT FOR THE WATER MAIN IS REQD.FROM
 THE DEPT.OF ENVIRONMENTAL PROTECTION AND
 P.B.COUNTY HEALTH DEPT.SUBMIT COPIES OF
 APPROVALS.COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.4.7.
  
 ALL BATHROOMS IN THECOVERED DWELL-
 ING UNITS SHALL COMPLY W/FEDERAL FAIR
 HOUSING ACT 24 CFR 100.205 (C)(3)(IV)
 REQ.#7(2),PARAGRAPH (A) 0R (B).CLEAR
 FLOOR SPACE SHALL BE SHOWN ON THE PLANS
 AND DESIGNATE WHICH DESIGN SPECIFICATION
 ("A" OR "B")OF THE FAIR HOUSING ACT IS
 BEING USED.
 ***NOTE:IF YOU CHOOSE SPECIFICATION "A",
 IT APPLIES TOALL BATHROOMS AND CLEAR
 FLOOR SPACE IS REQD.AT THE SHOWER.IN
 SPECIFICATION "B" BATHROOMS,ONLY ONE
 BATHING FIXTURE SHALL BE PROVIDED W/THE
 REQD.CLEAR FLOOR SPACE.A 30"X 48" CLEAR
 FLOOR SPACE IS REQD.ADJACENT TO THE
 BATHTUB.AS DESIGNED THE SHOWERS AND
 BATHTUBS DO NOT COMPLY W/THE ACT.