Plan Review Notes For Permit 99121241 |
Permit Number |
99121241 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | CONDENSATE DRAINS SHLL BE VENTED TO THE | | ATMOSPHERE PER COUNTYWIDE AMENDMENTS TO | | SPC SEC.804.3(5). | | | | WATER RISER FOR UNIT "D" DOESN'T MATCH | | THE ARCH.FLOOR PLAN.COUNTYWIDE | | AMENDMENTS TO SPC SEC.104.2.1. | | | | SHT.A-35 NOTES THAT BATHROOMS WILL BE | | DESIGNED UNDER THE FEDERAL FAIR | | HOUSING ACT REQ.#7(2)(A).THIS | | SPECIFICATION APPLIES TO ALL BATHROOMS, | | AND ALL FIXTURES IN THOSE BATHROOMS | | MUST BE USABLE.CLEAR FLOOR SPACE FOR | | FIXTURES AS ILLUSTRATED IN THE ACT SHALL | | BE PROVIDED.UNITS "C"AND "D" DO NOT | | COMPLY FOR THE BATHROOMS W/SHOWERS. | | | | A PERMIT FOR THE WATER MAIN IS REQD.FROM | | DEPT.OF ENVIRON.PROTECTION.SUBMIT COPY | | OF PERMIT FOR REVIEW.AN ADDITIONAL | | PERMIT MAY ALSO BEREQD.FROM P.B.COUNTY | | HEALTH DEPT.SUBMIT ALL REQD.APPROVALS | | SPC 1O1.4.7. |
|