Plan Review Notes
Plan Review Notes For Permit 99121241
Permit Number 99121241
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00CONDENSATE DRAINS SHLL BE VENTED TO THE
 ATMOSPHERE PER COUNTYWIDE AMENDMENTS TO
 SPC SEC.804.3(5).
  
 WATER RISER FOR UNIT "D" DOESN'T MATCH
 THE ARCH.FLOOR PLAN.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 SHT.A-35 NOTES THAT BATHROOMS WILL BE
 DESIGNED UNDER THE FEDERAL FAIR
 HOUSING ACT REQ.#7(2)(A).THIS
 SPECIFICATION APPLIES TO ALL BATHROOMS,
 AND ALL FIXTURES IN THOSE BATHROOMS
 MUST BE USABLE.CLEAR FLOOR SPACE FOR
 FIXTURES AS ILLUSTRATED IN THE ACT SHALL
 BE PROVIDED.UNITS "C"AND "D" DO NOT
 COMPLY FOR THE BATHROOMS W/SHOWERS.
  
 A PERMIT FOR THE WATER MAIN IS REQD.FROM
 DEPT.OF ENVIRON.PROTECTION.SUBMIT COPY
 OF PERMIT FOR REVIEW.AN ADDITIONAL
 PERMIT MAY ALSO BEREQD.FROM P.B.COUNTY
 HEALTH DEPT.SUBMIT ALL REQD.APPROVALS
 SPC 1O1.4.7.