Plan Review Notes
Plan Review Notes For Permit 99121241
Permit Number 99121241
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00CORRECTED BY REVISION 3/21/00***********
 1) SHT A-31 DETAIL 3 DRYER VENT AND BATH
 EXHAUST DUCT TO BE ENCLOSED IN SHAFT TO
 BOTTOM OF ROOF STRUCTURE.
 2) SHT A-31 DRYER VENT DUCT TO BE 4" NOT
 3".
 3) CONDENSATE DRAIN LINE SHALL NOT VENT
 INTO OCCUPIED SPACE. CARRY VENT THROUGH
 ROOF
 4) SHT AC-4 SHOWS DRYER VENT INTO SUB-
 DUCT. DRYER VENT TO RUN FULL LENGTH OUT
 OF BUILDING
 5) OVERFLOW PROTECTION REQUIRED FOR AHUS
 PER 1997 SMC 304.8.6