2001-01-08 00:00:00 | CORRECTED BY REVISION 3/21/00*********** | | 1) SHT A-31 DETAIL 3 DRYER VENT AND BATH | | EXHAUST DUCT TO BE ENCLOSED IN SHAFT TO | | BOTTOM OF ROOF STRUCTURE. | | 2) SHT A-31 DRYER VENT DUCT TO BE 4" NOT | | 3". | | 3) CONDENSATE DRAIN LINE SHALL NOT VENT | | INTO OCCUPIED SPACE. CARRY VENT THROUGH | | ROOF | | 4) SHT AC-4 SHOWS DRYER VENT INTO SUB- | | DUCT. DRYER VENT TO RUN FULL LENGTH OUT | | OF BUILDING | | 5) OVERFLOW PROTECTION REQUIRED FOR AHUS | | PER 1997 SMC 304.8.6 |
|