Plan Review Notes
Plan Review Notes For Permit 99121241
Permit Number 99121241
Review Stop B
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001. SHEET A-1 NOTE #4 SHOWS TYPE VI CONST
 TYPE VI CONST. NOT ALLOWED IN FIRST FIRE
 DISTRICT SEE APPENDIX F, 1997 SBC.
 2. REVISE SHEET A-1 TO REFLECT OPEANINGS
 SIZE ALLOWED BASED ON TYPE OF
 CONSTRUCTION USED SEE TABLE 600, 1997SBC
 3.REVISE EXTERIOR WALL DESIGN FOR FIRE
 DISTRICT BASED ON FIRE DISTRICT AND
 TABLE 600, 1997 SBC.
 4. SHEET A-2- INDICATES A DUCT BANK
 UNDER THE BUILDING NO EASEMENT RELEASES
 ON FILE. NO STRUCTURAL DETAILS ON PLANS.
 5. SHEET A-20 CHANGE REFERENCE FROM PALM
 BEACH COUNTY TO THE CITY OF WEST PALM
 BEACH.
 6. SUBMIT TRUSS DRAWINGS FOR REVIEW.
 7. PROVIDE PRODUCT APPROVAL INFORMATION
 FOR WINDOWS AND DOORS AS PER REQUIREMENT
 SHEET A-33.
 8. NOTE: CANOPIES, FENCES, GATES, SIGNS
 AND FOUNTIANS REQUIRE SEPERATE PERMITS.
 9. SHEET A-28 MAILBOXES UNDER STAIRS
 COMPLY WITH 1006.1.4, 1997 SBC
 10.SHEET A-29 SECTION A INDICATES WOOD
 FRAME ROOF SYSTEM ENERGY SHEET INDICATE
 CONCRETE ROOF WITH R10 INSULATION REVISE
 11. SHEET A-32 INDICATES IN NOTES THAT
 MISSLE IMPACT NOTES ARE ON SHEET A-27.
 A-27 DOES NOT CONTAIN THE INFORMATION
 PROPER REFERENCE IS A-33.
 12. SHEET A-32 DOOR SCHEDULE DOORS DO
 NOT MATCH ELEVATION SEE DOOR #7.
 13. SHEET A-33 CODE REFERENCE FOR MISSLE
 IMPACT AND WIND DESIGN IS NOT CORRECT
 INDICATES 1994 SBC SHOULD BE 1997 SBC.
 14. SHEET A-35 REFERENCES WRONG EDITION
 OF THE FAIR HOUSING ACT.
 15. SHEET S-9 SECTION 7 INDICATES A
 1 1/2" OFFSET, SHEET A-32 SECTION 5
 INDICATES 1/2" AND COMPLIES WITH FAIR
 HOUSING ACT DOORS.
 16. SHEET S-12 DOES NOT INDICATE CODE
 EDITION (1997) OR METHOUD OF COMPLIANCE
 1606 OR ASCE-7-95 FOR BUILDING DESIGN.