2001-01-08 00:00:00 | 1. SHEET A-1 NOTE #4 SHOWS TYPE VI CONST |
| TYPE VI CONST. NOT ALLOWED IN FIRST FIRE |
| DISTRICT SEE APPENDIX F, 1997 SBC. |
| 2. REVISE SHEET A-1 TO REFLECT OPEANINGS |
| SIZE ALLOWED BASED ON TYPE OF |
| CONSTRUCTION USED SEE TABLE 600, 1997SBC |
| 3.REVISE EXTERIOR WALL DESIGN FOR FIRE |
| DISTRICT BASED ON FIRE DISTRICT AND |
| TABLE 600, 1997 SBC. |
| 4. SHEET A-2- INDICATES A DUCT BANK |
| UNDER THE BUILDING NO EASEMENT RELEASES |
| ON FILE. NO STRUCTURAL DETAILS ON PLANS. |
| 5. SHEET A-20 CHANGE REFERENCE FROM PALM |
| BEACH COUNTY TO THE CITY OF WEST PALM |
| BEACH. |
| 6. SUBMIT TRUSS DRAWINGS FOR REVIEW. |
| 7. PROVIDE PRODUCT APPROVAL INFORMATION |
| FOR WINDOWS AND DOORS AS PER REQUIREMENT |
| SHEET A-33. |
| 8. NOTE: CANOPIES, FENCES, GATES, SIGNS |
| AND FOUNTIANS REQUIRE SEPERATE PERMITS. |
| 9. SHEET A-28 MAILBOXES UNDER STAIRS |
| COMPLY WITH 1006.1.4, 1997 SBC |
| 10.SHEET A-29 SECTION A INDICATES WOOD |
| FRAME ROOF SYSTEM ENERGY SHEET INDICATE |
| CONCRETE ROOF WITH R10 INSULATION REVISE |
| 11. SHEET A-32 INDICATES IN NOTES THAT |
| MISSLE IMPACT NOTES ARE ON SHEET A-27. |
| A-27 DOES NOT CONTAIN THE INFORMATION |
| PROPER REFERENCE IS A-33. |
| 12. SHEET A-32 DOOR SCHEDULE DOORS DO |
| NOT MATCH ELEVATION SEE DOOR #7. |
| 13. SHEET A-33 CODE REFERENCE FOR MISSLE |
| IMPACT AND WIND DESIGN IS NOT CORRECT |
| INDICATES 1994 SBC SHOULD BE 1997 SBC. |
| 14. SHEET A-35 REFERENCES WRONG EDITION |
| OF THE FAIR HOUSING ACT. |
| 15. SHEET S-9 SECTION 7 INDICATES A |
| 1 1/2" OFFSET, SHEET A-32 SECTION 5 |
| INDICATES 1/2" AND COMPLIES WITH FAIR |
| HOUSING ACT DOORS. |
| 16. SHEET S-12 DOES NOT INDICATE CODE |
| EDITION (1997) OR METHOUD OF COMPLIANCE |
| 1606 OR ASCE-7-95 FOR BUILDING DESIGN. |