 CONDENSATE SYSTEM FOR MULTIPLE UNITS
 SHALL BE VENTED TO THE ATMOSPHERE PER
 COUNYUWIDE AMENDMENTS TO SPC SEC.804.3.
 (5).
  
 WATER RISER FOR UNIT "A"DOESN'T
 CORRELATE W/ARCH.FLOOR PLAN. COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 SHT.A-35 NOTES THAT BATHROOMS WILL BE
 DESIGNED UNDER THE FEDERAL FAIR HOUSING
 ACT REQ.#7(2)(A).THIS SPECIFICATION
 APPLIES TO ALL BATHROOMS,AND ALL
 FIXTURES IN THOSE BATHROOMS MUST BE
 USABLE.CLEAR FLOOR SPACE FOR FIXTURES
 SHALL BE PROVIDED.UNITS "C" AND "D" DO
 NOT COMPLY FOR BATHROOMS WITH SHOWERS.
  
 A PERMIT FOR THE WATER MAIN IS REQD.FROM
 DEPT.OF ENVIRON.PROTECTION.SUBMIT COPY
 OF PERMIT FOR REVIEW.AN ADDITIONAL
 PERMIT MAY ALSO BE REQD.FROM P.B.COUNTY
 HEALTH DEPT.SUBMIT ALL REQD.APPROVALS.