Plan Review Notes For Permit 99121238 |
Permit Number |
99121238 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | CORRECTED BY REVISIONS 3/21/00********** | | 1) SHT A-31 DETAIL 3 DYER VENT AND BATH | | EXHAUST DUCT TO BE ENCLOSED IN SHAFT TO | | BOTTOM OF ROOF STRUCTUR | | 2) SHT A-31 DETAIL 2 DRYER VENT TO BE | | MIN. 4" NOT 3", DRYER VENT TO RUN FULL | | LENGTH OUT OF BUILDING | | 3) SHT A-31 DETAIL 4 INDICATE WHICH SIZE | | CAP TO BE USED- 4" OR 2 1/2" NOTE: FLEX | | METAL DUCT NOT ALLOWED BY CODE | | 4) CONDENSING UNIT SERVICE TO BE PER NEC | | AND 1997 SMC 304.7.2 WHICHEVER IS GREATE | | DISCONNECT TO BE WITHIN 6' OF THE SERVIC | | SIDE OF THE EQUIPMENT AND A 115V GFCI | | OUTLET REQUIRED | | 5) SHT AC 5 OVERFLOW PROTECTION REQUIRED | | FOR AHU'S PER 1997 SMC 304.8.6 |
|