2001-01-08 00:00:001. SHEET A-1 NOTE #4 SHOWS TYPE VI CONST
 TYPE VI CONST. NOT ALLOWED IN FIRST FIRE
 DISTRICT SEE APPENDIX F, 1997 SBC.
 2. REVISE SHEET A-1 TO REFLECT OPEANINGS
 SIZE ALLOWED BASED ON TYPE OF
 CONSTRUCTION USED SEE TABLE 600, 1997SBC
 3. REVISE EXTERIOR WALL DESIGN FOR FIRE
 DESTRICT BASED ON FIRE DESTRICT AND
 TABLE 600, 1997 SBC.
 4. SHEET A-24 NOTES REFER TO SHEET A-27
 SHEET NOT IN PLANS.
 5. SUBMIT TRUSS DRAWINGS FOR REVIEW.
 6. PROVIDE PRODUCT APPROVAL INFORMATION
 FOR WINDOWS AND DOORS AS PER SHEET A-33.
 7. CANOPIES, FENCES, GATES, SIGNS AND
 FOUNTIANS REQUIRE SEPERATE PERMITS SEE
 SHEET A-41.
 8. SHEET A-28 MAILBOXES UNDER STAIRS
 COMPLY WITH 1006.1.4, 1997 SBC.
 9. SHEET A-29 SECTION A ETC. INDICATES
 WOOD FRAME ROOF SYSTEM ENERGY SHEET
 INDICATES CONCRETE ROOF WITH R10
 INSULATION.
 10. SHEET A-32 INDICATES IN NOTES THAT
 MISSLE IMPACT NOTES ARE ON SHEET A-27.
 A-27 DOES NOT CONTAIN THE INFORMATION
 PROPER REFRENCE IS A-33.
 11. SHEET A-32 DOOR SCHEDULE DOORS DO
 NOT MATCH ELEVATIONS SEE DOOR #7.
 12. SHEET A-33 CODE REFERENCE FOR MISSLE
 IMPACT AND WIND DESIGN IS NOT CORRECT
 PLAN INDICATES 1994 SBC SHOULD BE
 1997 SBC.
 13. SHEET A-35 REFERENCES THE WRONG
 EDITION OF THE FAIR HOUSING ACT.
 14. SHEET S-9 SECTION 7 INDICATES A
 1 1/2" OFFSET, SHEET A-32 SECTION 5
 INDICATES 1/2" AND COMPLIES WITH FAIR
 HOUSING ACT. (DOORS)
 15. SHEET S-12 DOES NOT INDICATE CODE
 EDITION (1997) OR METHOUD OF COMPLIANCE
 1606 OR ASCE 7-95 FOR BUILDING DESIGN.