Plan Review Notes For Permit 99121237 |
Permit Number |
99121237 |
|
Review Stop |
FIRE |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1) BUILDING ADDRESS NOT SHOWN ON | | ELEVATION DRAWINGS. BUILDING ADDRESS TO | | COMPLY WITH CITY CODE REQUIREMENTS. | | 2) EXIT DOOR 101 AND 117 ARE NOT TO | | INTERFERE WITH ONE ANOTHER WHEN BOTH | | ARE OPENED. | | 3) HANDRAILS AND GUARDS TO COMPLY WITH | | NFPA 101, THE LIFE SAFETY CODE, 1985 | | EDTION. | | 4) PROVIDE COMPLETE FIRE ALARM SYSTEM | | SHOP DRAWINGS AND CUT SHEETS FOR FIRE | | ALARM EQUIPMENT SHOWN ON DRAWINGS. | | 5) ELEVATOR TO COMPLY WITH ANSI A17.1 | | 6) STAIRS TO COMPLY WITH NEW STAIR | | REQUIREMENTS IN NFPA 101, THE LIFE | | SAFETY CODE, 1985 EDITION. | | APPROVED PROVISO: |
|