2001-01-08 00:00:00 | SUBMIT DETAIL OF SCUPPERS.COMPLY W/ | | APPENDIX "A",TABLE A101.2. | | | | SUBMIT COMPLETE STORM RISER DIAGRAM FOR | | REVIEW.SHOW SQ.FT.AREA DRAINED BY EACH | | DRAIN.COMPLY W/SPC SEC.1108.1,1108.2. | | SIZING SHALL INCUDE 1/2 TOTAL AREA OF | | PARAPET WALLS PER SPC SEC.1108.3. | | | | SIZING OF SECONDARY DRAINAGE SYSTEM | | SHALL COMPLY W/SPC SEC.1109.3.SUBMIT | | CALCULATIONS FOR REVIEW. | | | | INDICATE SLOPE OF STORM DRAINAGE PIPING | | ON PLANS.COMPLY W/TABLES 1108.1,1108.2. |
|