2001-01-08 00:00:00**********PROVISO***********************
 1) 1997 SMC 505 AND NFPA 96 TO BE REFERE
 FOR COMPLIANCE WITH THE TENANT KITCHEN
 EXHAUST
 2) EXHAUST SHAFT TO BE FOR EXHAUST DUCT
 ONLY AND NOT USED FOR ANY OTHER PURPOSE
 3) EXHAUST DUCT TO HAVE CLEANOUT PROVIS-
 IONS AT EACH FLOOR AS WELL AS CHANGE OF
 DIRECTION