Plan Review Notes
Plan Review Notes For Permit 99121236
Permit Number 99121236
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SHT.P-2-CONDENSATE LINES ARE SHOWN AS 2"
 AND AS 1 1/4".CLARIFY.
  
 SHT.P-2-SUBMIT A SANITARY ISOMETRIC THAT
 IS LEGIBLE AND CLEARLY REFLECTS THE
 SCOPE OF THE INSTALLATION PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.(SUBMIT
 ONE LAYOUT OF THE UNITS AND SEWER.DELETE
 ALTERNATES.)
  
 ENERGY CALCS.NOTE EWH AS 60 GALS.AND SHT
 P-1 NOTES 30 GAL.CLARIFY.FEC.SEC.103.2.
 (SEE SHT.7.)
  
 CONDENSATE DRAINS ON MULTIPLE STORY
 BUILDINGS SHALL BE VENTED WHERE 2 OR
 MORE UNITS ARE CONNECTED TO A COMMON
 RISER PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.804.3(5).
  
 SUBMIT CONDENSATE RISER FOR REVIEW PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 SUBMIT IRRIGATION PLANS IF APPLICABLE
 AND INDICATE WATER SUPPLY SOURCE FOR
 SYSTEM.A WATER USE PERMIT MAY BE REQD.
 FROM SFWMD PER F.S.373.219.
  
 CIVIL DRAWINGS SHALL BE SEALED PER F.S.
 471.025,104.2.3.
  
 NOTE:SEPARATE PERMITS SHALL BE REQD.FOR
 THE POOL,FOUNTAIN AND CABANA.
  
 A PERMITIS REQUIRED FROM THE DEPT.OF
 ENVIRONMENTAL PROTECTION (DEP) FOR THE
 WATER AND SEWER MAINS.