Plan Review Notes For Permit 99121236 |
Permit Number |
99121236 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | SHT.P-2-CONDENSATE LINES ARE SHOWN AS 2" | | AND AS 1 1/4".CLARIFY. | | | | SHT.P-2-SUBMIT A SANITARY ISOMETRIC THAT | | IS LEGIBLE AND CLEARLY REFLECTS THE | | SCOPE OF THE INSTALLATION PER COUNTYWIDE | | AMENDMENTS TO SPC SEC.104.2.1.(SUBMIT | | ONE LAYOUT OF THE UNITS AND SEWER.DELETE | | ALTERNATES.) | | | | ENERGY CALCS.NOTE EWH AS 60 GALS.AND SHT | | P-1 NOTES 30 GAL.CLARIFY.FEC.SEC.103.2. | | (SEE SHT.7.) | | | | CONDENSATE DRAINS ON MULTIPLE STORY | | BUILDINGS SHALL BE VENTED WHERE 2 OR | | MORE UNITS ARE CONNECTED TO A COMMON | | RISER PER COUNTYWIDE AMENDMENTS TO SPC | | SEC.804.3(5). | | | | SUBMIT CONDENSATE RISER FOR REVIEW PER | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | | SUBMIT IRRIGATION PLANS IF APPLICABLE | | AND INDICATE WATER SUPPLY SOURCE FOR | | SYSTEM.A WATER USE PERMIT MAY BE REQD. | | FROM SFWMD PER F.S.373.219. | | | | CIVIL DRAWINGS SHALL BE SEALED PER F.S. | | 471.025,104.2.3. | | | | NOTE:SEPARATE PERMITS SHALL BE REQD.FOR | | THE POOL,FOUNTAIN AND CABANA. | | | | A PERMITIS REQUIRED FROM THE DEPT.OF | | ENVIRONMENTAL PROTECTION (DEP) FOR THE | | WATER AND SEWER MAINS. |
|