Plan Review Notes For Permit 99121045 |
Permit Number |
99121045 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | *************PROVISO******************** | | | | 1)NOTE:AS REQ`D BY ART;250-81/215-5 | | NEED TO SHOW COLD WATER PIPE AS PART OF | | THE GROUNDING ELECTRODE SYSTEM. | | | | 2)NOTE:MISSING OUTLET AS PER 210-52 | | | | 3)NOTE: MAIN DISCONNECT IS DRAWN ON | | PLANS?? IF THERE IS GOING TO BE A MAIN | | DISC. THEN PLEASE HAVE DRAWN ON RISER | | DIAGRAM AS REQ`D BY 215-5 | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | FOR REVIEW AND APPROVAL BEFORE FIRST | | ROUGH ELECTRICAL INSPECTION IS CALLED IN | | IF THERE ARE ANY QUESTIONS;659-8096 | | EXT 8372 |
|