Plan Review Notes
Plan Review Notes For Permit 99120985
Permit Number 99120985
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT MANUF.SHEETS FOR POOL HTR.HEATER
 SHALL BE LISTED.SGC SEC.402.1.
  
 SHOW CORRECT BTU LOAD AND TYPE OF PIPING
 TO BE INSTALLED.SGC 305.4.
  
 BYPASS REQD.ON POOL HTR.PER NFPA 54 SEC.
 6.22.4.
  
 SHOW TOTAL LENGTH OF PIPE TO MOST REMOTE
 OUTLET PER SGC SEC.305.4.