Plan Review Notes For Permit 99120679 |
Permit Number |
99120679 |
|
Review Stop |
R |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | 1-REVISE THE DESIGN CERTIFICATION FOR | | BUILDING CODE COMPLIANCE FORM. THE | | MEAN ROOF HEIGHT IS TAKEN FROM GRADE, | | NOT FROM FINISH FLOOR, TO THE AVERAGE | | POINT OF THE HIGHEST ROOF. THEREFORE, | | THE MEAN ROOF HEIGHT FOR THIS BUILDING | | IS PLUS OR MINUS 19'-4". | | NOTE: REVISE DRAWING #1 AS WELL. | | 2-PROVIDE COPIES OF THE APPROVED DRAWING | | FOR ENTRY DOORS PRODUCT APPROVAL. | | 3-PROVIDE SOIL TEST REPORT. | | NOTE: SEE SECTION 1804.2.7.2 OF CITY | | AMENDMENTS FOR MINIMUN REQUIREMENTS. | | -PROVIDE TWO COPIES OF SOIL TEST REPORT | | SIGNED, SEALED AND DATED. (EMBOSSED | | SEAL). | | 4-STORM PANELS: | | -UPDATE INSTALLATION SCHEDULE AND KEY | | PLAN TO MATCH ARCHITECT'S FLOOR PLAN | | AND EXTERIOR ELEVATIONS. | | -REVISE PANELS #2 AND #16. PANELS THAT | | ARE LONGER 9'-4" SHALL BE BOLTED. SEE | | NOTE #7 ON GENERAL NOTES OF PRODUCT | | APPROVAL, SHEET 1 OF 8. | | -SPECIFY ANCHOR SPACING FOR PANELS THAT | | ARE LONGER THAN 8'-0". |
|