2001-01-08 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING STAMPED DRAWINGS AND RECEIPT.
 2-EGRESS OPENING FROM "ATRIUM" AREA TO
 HAVE 5 SQUARE FEET OF CLEAR OPENING
 MINIMUM. SEC 1005.4.4 SBC 1997.
 -TOP OF PRIVACY WALL AT "ATRIUM" TO BE
 UP TO THE BOTTOM OF LINTEL OF SLIDING
 GLASS DOOR. REVISE HEIGHT AS REQUIRED.
 3-PROVIDE COMPLETE DETAILS FOR
 INSTALLATION OF AHU HUNG FROM TRUSSES.
 SPECIFY ALL CONNECTORS.
 4-ENERGY CALCULATIONS TAKE CREDIT FOR
 CEILING FANS. SPECIFY SIZES OF FANS AS
 PER TABLE 6-6 OF FLORIDA ENERGY CODE
 1997 EDITION.
 5-REVISE WIND LOAD CERTIFICATION FORM
 AS REQUIRED.
 6-ENERGY CALCULATIONS TO BE SITE
 SPECIFIC. FILL IN ALL INFORMATION ON
 TOP PORTION OF FORM 600A-97 AND
 OWNER/AGENT TO SIGN AND DATE FORM AS
 WELL.
 -NOTE: THE CLIMATE ZONE IS #8 NOT
 SOUTH. SOUTH IS THE REGION. REVISE AS
 REQUIRED.
 7-PROVIDE PRODUCT APPROVAL FOR ROOF TILE
 AND CLEARLY SPECIFY FASTENING METHOD.
 -SEE COMMENTS ON FRONT PAGE OF ALL
 PRODUCT APPROVALS SUBMITTED AND
 HIGHLIGHT THE COMPONENTS AS REQUIRED.
 8-SEE COMMENTS ON ARCHITECTURAL PLANS
 AND REVISE/UPDATE DRAWINGS AS REQUIRED
 9-PROVIDE SOIL TEST REPORT.
 10-OWES $470.05 TO THE CITY OF WEST PALM
 BEACH FOR LOW VALUATION AND RADON FEES
 11-STORM PANELS:
 -PROVIDE A COMPLETE INSTALLATION
 SCHEDULE (AS PER CITY SAMPLE) AND KEY
 PLAN.
 -HIGHLIGHT SPECIFIC MOUNTING CONDITIONS
 USED IN THIS PROJECT.
 -HIGHLIGHT SPECIFIC ANCHORS TO BE USED
 ACCORDING TO THE DESIGN PRESSURES,
 PANEL SPAN, BUILDING CONSTRUCTION ETC.
 NOTE: THIS BUILDING IS MASONRY
 CONSTRUCTION. USE ANCHORS AS REQUIRED.