2001-01-08 00:00:00CONTINUATION OF PLBG.COMMENTS:
  
 SHT.P-13-FLOOR DRAINS NOT PROPERLY
 VENTED.SPC SEC.901.2.
  
 SHT.P-16-JOINTS ON WATER DISTRIBUTION
 SYSTEM NOT PERMITTED UNDER SLAB INSIDE
 BUILDING PER COUNTYWIDE AMENDMENTS SEC.
 611.3.SEE DETAIL #4.
  
 FIXTURES HAVING SLIP JOINT CONNECTIONS
 SHALL COMPLY W/SPC SEC.401.5.2.(SEE
 SHT.P-16,DETAIL #1.
  
 MINIMUM SIZE OF DRAINAGE PIPE UNDER-
 GROUND SHALL BE 2" PER SPC SEC.714.4.
  
 BACKWATER VALVES SHALL BE INSTALLED ON
 DRAIN CONNECTIONS FROM FOUNTAINS TO
 STORM SYSTEM PER SPC 301.11.1,409.9.2.
  
 SHTS.A1.32-ROOM#1627 & A1.34 &1.36-ROOM
 #1647-SHOWERS SHALL COMPLY W/FACBC SECS.
 4.21.2-4.21.8.WASHER AND DRYER SHALL
 COMPLY W/FACBC SEC.6.1(1).
  
 VOID ALL PREVIOUS PLBG.SHEETS REPLACED
 BY NEW REVISIONS AND INSERT NEW SHEETS
 INTO PLANS .COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 SHT.P24-VENT SIZING SHALL COMPLY W/SPC
 TABLE 920.2,920.4.
  
 SHT.P24-THE SANITARY SCHEMATIC IS VAGUE
 REGARDING THE LINE SIZES FOR THE DRAIN-
 AGE SYSTEM.THERE ARE SECTIONS WITH NO
 SIZES,LONG RUNS W/NO SIZES,
  
 SHT.P24-HORIZONTAL DRAIN PIPING LACKS
 SIZES AND SCHEMATIC DOESN'T REFLECT
 THE SYSTEM AS DRAWN ON SHTS.P3 & P4.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 VENTS NOT PERMITTED TO INCREASE IN SIZE.
 SPC 905.2.(PERMITTED ONLY WHERE FROST
 CLOSURE IS A PROBLEM.)
  
 NOTE:I RECOMMEND A MEETING W/THE DESIGN
 PROFESSIONALS AND MYSELF TO CLARIFY
 ISSUES,EPECIALLY THE PLUMBING SCHEMATIC.
  
 PLEASE CALL 561-659-8096 EXT.8377 IF YOU
 HAVE ANY QUESTIONS.
 TIMOTHY K.LARGE,PLUMBING PLAN REVIEW.