2001-01-08 00:00:00 | JOB SPEC.15400-1.3-DELETE REFERENCE TO |
| 1997 EDITION OF STANDARD PLUMBING CODE. |
| THE 1994 EDITION IS THE ADOPTED STANDARD |
| |
| SPEC.15141-3.1(A)(B)-HANGERS & SUPPORTS |
| FOR PIPING SHALL COMPLY W/SPC SEC.310.2, |
| 310.3. |
| |
| SPEC.15412-3.7(A)-SIZE AND SPACING OF |
| CLEANOUTS IN THE SANITARY SYSTEM SHALL |
| COMPLY W/SPC SEC.710.2.1-710.2.4,711.1, |
| 711.2.,712. |
| |
| SUBMIT APPROVALS FROM CITY OF WEST PALM |
| BEACH ENGINEERING DEPT.FOR STORM |
| DRAINAGE SYSTEM.COUNTYWIDE AMENDMENTS TO |
| SPC SEC.101.4.7. |
| |
| SUBMIT COPIES OF APPROVALS FROM PALM |
| BEACH COUNTY HEALTH DEPT.AND DEP FOR |
| WATER MAIN/WATER SERVICE EXTENSION. |
| COUNTYWIDE AMENDMENTS TO SPC SEC.101.4.7 |
| |
| INDICATE WATER SOURCE FOR IRRIGATION |
| SYSTEM.IF SUPPLY IS FROM AN ARTIFICIAL |
| MEANS(WELL,LAKE,ETC.)A WATER USE PERMIT |
| WILL BE REQD.FROM SO.FLA.WATER MNGMT. |
| PER F.S.373.219. |
| |
| SUBMIT COPY OF AHCA APPROVAL FOR THIS |
| PROJECT.COUNTYWIDE AMENDMENTS TO SPC |
| SEC.101.4.7. |
| |
| NOTE OCCUPANT LOAD FOR THE STRUCTURE |
| BASED UPON SQ.FOOTAGE.REFER TO SPC SEC. |
| 407.1.3 AND TABLE 407. |
| |
| SHT.C1.00-SHOW SQ.FOOT AREA DRAINED BY |
| EACH AREA DRAIN.COMPLY W/SPC TABLE |
| 1108.2. |
| |
| SHT.C2.00-LOCATION OF BFP DEVICE SHALL |
| BE APPROVED BY CITY OF WPB UTILITIES. |
| CALL 659-8000,EXT.2008. |
| |
| REFER TO "A"DRAWINGS-REVISE NOTES THAT |
| REFER TO 1997 EDITION OF STD.PLBG.CODE |
| TO READ 1994 EDITION.AMENDMENTS TO SPC |
| SECS.101.1,101.2. |
| |
| REFER TO "A" DRAWINGS -THERE ARE STILL |
| SHEETS THAT DO NOT SHOW LAVATORIES IN |
| THE HANDICAP ACCESSIBLE STALLS.SEE A7.7, |
| A7.13, |
| |
| SHT.A6.9-SHOW CLEAR FLOOR SPACE UNDER |
| H.C.LAV.COMPLY W/FACBC SEC.4.19.2(MIN. |
| 29" REQD.). |
| |
| MEDICAL CARE FACILITIES SHALL COMPLY W/ |
| FACBC SECS.6.1(1) FLA.10% RULE,6.4,4.22, |
| 4.23.THE STRUCTURE DOES NOT PRESENTLY |
| COMPLY. |
| |
| BATHTUBS LOCATED IN HANDICAP ACCESSIBLE |
| PATIENT ROOMS SHALL COMPLY W/FACBC SECS. |
| 4.20.1-4.20.7. |
| |
| SHT.A6.1-GRAB BARS FOR TUB W/SEAT AT |
| HEAD SHALL COMPLY W/FACBC FIG.34. |
| |
| SHT.A6.1-MOUNTING HEIGHTS OF MIRRORS, |
| TOWEL DISPENSERS,ETC.SHALL COMPLY W/ |
| FACBC SEC.4.2.5,4.2.6,4.19.6,4.23.9, |
| & FIGS.5 & 6. |
| |
| SUBMIT DETAILS/CALCULATIONS FOR |
| SECONDARY ROOF DRAINAGE.(REFER TO ROOFS |
| FOR FLOORS #1,2,3,& 5.COMPLY W/SPC SEC. |
| 1109.1-1109.3,APPENDIX "A",AND SBC SECS. |
| 1517.6.4.1.-1517.6.4.3. |
| |
| SHT.A1.30-ROOM 1631-SHOWER FLOOR SHALL |
| BE DRAINED TO COMPLY W/SPC SEC.409.8.3. |
| |
| EFFLUENT FROM ELEVATOR SUMP SHALL FIRST |
| PASS THRU AN OIL INTERCEPTOR AND THEN TO |
| THE SANITARY SYSTEM BY INDIRECT CONNECT- |
| ION PER SPC SEC 301.4,1004.1,1004.5 & |
| FLA.ADMIN.CODE CHAPT.61(C)-5.OO1 |
| |
| FILM PROCESSORS UTILIZING WATER AND |
| WASTE CONNECTIONS SHALL COMPLY W/SPC |
| SECS.606.1,801.4. |
| |
| SHT.P-14-CLEANOUT PLUG SHOWN IN SHOWER |
| DRAIN.PLUG SHALL BE ACCESSIBLE PER SPC |
| SEC.710.6.1. |
| |
| SEE PLBG.STEP #6 FOR CONTINUATION. |