Plan Review Notes
Plan Review Notes For Permit 99120645
Permit Number 99120645
Review Stop P
Sequence Number 5
Notes
Date Text
2001-01-08 00:00:00JOB SPEC.15400-1.3-DELETE REFERENCE TO
 1997 EDITION OF STANDARD PLUMBING CODE.
 THE 1994 EDITION IS THE ADOPTED STANDARD
  
 SPEC.15141-3.1(A)(B)-HANGERS & SUPPORTS
 FOR PIPING SHALL COMPLY W/SPC SEC.310.2,
 310.3.
  
 SPEC.15412-3.7(A)-SIZE AND SPACING OF
 CLEANOUTS IN THE SANITARY SYSTEM SHALL
 COMPLY W/SPC SEC.710.2.1-710.2.4,711.1,
 711.2.,712.
  
 SUBMIT APPROVALS FROM CITY OF WEST PALM
 BEACH ENGINEERING DEPT.FOR STORM
 DRAINAGE SYSTEM.COUNTYWIDE AMENDMENTS TO
 SPC SEC.101.4.7.
  
 SUBMIT COPIES OF APPROVALS FROM PALM
 BEACH COUNTY HEALTH DEPT.AND DEP FOR
 WATER MAIN/WATER SERVICE EXTENSION.
 COUNTYWIDE AMENDMENTS TO SPC SEC.101.4.7
  
 INDICATE WATER SOURCE FOR IRRIGATION
 SYSTEM.IF SUPPLY IS FROM AN ARTIFICIAL
 MEANS(WELL,LAKE,ETC.)A WATER USE PERMIT
 WILL BE REQD.FROM SO.FLA.WATER MNGMT.
 PER F.S.373.219.
  
 SUBMIT COPY OF AHCA APPROVAL FOR THIS
 PROJECT.COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.4.7.
  
 NOTE OCCUPANT LOAD FOR THE STRUCTURE
 BASED UPON SQ.FOOTAGE.REFER TO SPC SEC.
 407.1.3 AND TABLE 407.
  
 SHT.C1.00-SHOW SQ.FOOT AREA DRAINED BY
 EACH AREA DRAIN.COMPLY W/SPC TABLE
 1108.2.
  
 SHT.C2.00-LOCATION OF BFP DEVICE SHALL
 BE APPROVED BY CITY OF WPB UTILITIES.
 CALL 659-8000,EXT.2008.
  
 REFER TO "A"DRAWINGS-REVISE NOTES THAT
 REFER TO 1997 EDITION OF STD.PLBG.CODE
 TO READ 1994 EDITION.AMENDMENTS TO SPC
 SECS.101.1,101.2.
  
 REFER TO "A" DRAWINGS -THERE ARE STILL
 SHEETS THAT DO NOT SHOW LAVATORIES IN
 THE HANDICAP ACCESSIBLE STALLS.SEE A7.7,
 A7.13,
  
 SHT.A6.9-SHOW CLEAR FLOOR SPACE UNDER
 H.C.LAV.COMPLY W/FACBC SEC.4.19.2(MIN.
 29" REQD.).
  
 MEDICAL CARE FACILITIES SHALL COMPLY W/
 FACBC SECS.6.1(1) FLA.10% RULE,6.4,4.22,
 4.23.THE STRUCTURE DOES NOT PRESENTLY
 COMPLY.
  
 BATHTUBS LOCATED IN HANDICAP ACCESSIBLE
 PATIENT ROOMS SHALL COMPLY W/FACBC SECS.
 4.20.1-4.20.7.
  
 SHT.A6.1-GRAB BARS FOR TUB W/SEAT AT
 HEAD SHALL COMPLY W/FACBC FIG.34.
  
 SHT.A6.1-MOUNTING HEIGHTS OF MIRRORS,
 TOWEL DISPENSERS,ETC.SHALL COMPLY W/
 FACBC SEC.4.2.5,4.2.6,4.19.6,4.23.9,
 & FIGS.5 & 6.
  
 SUBMIT DETAILS/CALCULATIONS FOR
 SECONDARY ROOF DRAINAGE.(REFER TO ROOFS
 FOR FLOORS #1,2,3,& 5.COMPLY W/SPC SEC.
 1109.1-1109.3,APPENDIX "A",AND SBC SECS.
 1517.6.4.1.-1517.6.4.3.
  
 SHT.A1.30-ROOM 1631-SHOWER FLOOR SHALL
 BE DRAINED TO COMPLY W/SPC SEC.409.8.3.
  
 EFFLUENT FROM ELEVATOR SUMP SHALL FIRST
 PASS THRU AN OIL INTERCEPTOR AND THEN TO
 THE SANITARY SYSTEM BY INDIRECT CONNECT-
 ION PER SPC SEC 301.4,1004.1,1004.5 &
 FLA.ADMIN.CODE CHAPT.61(C)-5.OO1
  
 FILM PROCESSORS UTILIZING WATER AND
 WASTE CONNECTIONS SHALL COMPLY W/SPC
 SECS.606.1,801.4.
  
 SHT.P-14-CLEANOUT PLUG SHOWN IN SHOWER
 DRAIN.PLUG SHALL BE ACCESSIBLE PER SPC
 SEC.710.6.1.
  
 SEE PLBG.STEP #6 FOR CONTINUATION.