2001-01-08 00:00:00 | THESE COMMENTS ARE A CONTINUATION OF THE |
| PLUMBING PLAN REVIEW FOR THIS PROJECT. |
| |
| SUBMIT COPY OF AHCA APPROVAL FOR THIS |
| PROJECT.COUNTYWIDE AMENDMENTS TO SPC |
| SEC.101.4.7. |
| |
| SUBMIT APPROVAL FROM SO.FLA.WATER MNGMT. |
| FOR INSTALLATION OF DRAINAGE WORK.COUNTY |
| WIDE AMENDMENTS TO SPC SEC.101.4.7. |
| |
| SUBMIT COMPLETE ISOMETRIC DIAGRAMS FOR |
| THE INSTALLATION OF THE SANITARY,STORM, |
| AND WATER SYSTEMS.THE DRAWINGS SHALL |
| CLEARLY REFLECT THE ENTIRE SCOPE OF |
| PLUMBING WORK BEING DONE.(INCLUDE ALL |
| UNDERGROUND WORK ON THE ISOMETRICS.) |
| COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.2 |
| |
| INDICATE SLOPE OF PIPE ON THE PLANS FOR |
| THE STORM DRAINAGE SYSTEM.COMPLY W/TABLE |
| 1108.2 OF SPC. |
| |
| DISCHARGE LINE FROM ELEVATOR SUMP SHALL |
| CONNECT INDIRECTLY TO THE STORM DRAIN |
| SYSTEM.FLA.ADMIN.CODE CHAPT.61(C)-5.001. |
| |
| THE SHUT-OFF AND CHECK VALVES FOR THE |
| ELEVATOR SUMP SHALL BE LOCATED ABOVE THE |
| SUMP COVER AND BE ACCESSIBLE PER SPC |
| SEC.717.2. |
| |
| SUBMIT REVISED BLUEPRINTS SHOWING |
| LAVATORIES WITHIN THE REQD.ACCESSIBLE |
| STALLS.THE DIMENSIONS OF THE STALL SHALL |
| COMPLY W/FACBC SEC.4.17.3.(MIN.81"WIDE.) |
| |
| SHT.P-13-SUBMIT DETAILS FOR THE WATER |
| FILL LINE TO THE FOUNTAIN.SHOW REQD. |
| BACKFLOW PROTECTION OF THE WATER SYSTEM. |
| SPC 606.1,606.2 |
| |
| SHT.P-16-FIXTURES HAVING CONCEALED SLIP |
| JOINT CONNECTIONS SHALL COMPLY W/SPC |
| 401.2.2.(SEE DETAIL #2) |
| |
| SHT.18-DETAIL#3-VENT SIZING SHALL COMPLY |
| W/SPC SEC.920.2.(FIXTURE UNIT LOAD |
| EXCEEDS 2" CAPACITY.)CHECK ALL RISERS |
| FOR PROPER VENT SIZING PER SPC 920.2. |
| |
| SUBMIT CONDENSATE RISER FOR REVIEW. |
| COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 |
| |
| SUBMIT MANUF.SHEETS FOR FILM PROCESSOR. |
| WATER CONNECTION SHALL BE PROTECTED |
| AGAINST BACKFLOW AND EFFLUENT SHALL |
| BE NEUTRALIZED PRIOR TO DISCHARGE TO |
| SANITARY SYSTEM.SPC SEC.606.1,801.4. |
| |
| SUBMIT PLANS FOR IRRIGATION SYSTEM.SHOW |
| WATER SOURCE AND PROTECTION AGAINST |
| BACKFLOW PER SPC 606.1 |
| |
| A PERMIT MAY BE REQD.FOR THE WATER |
| SERVICE FROM DEPT.OF ENVIRON.PROTECTION |
| & HEALTH DEPT.SUBMIT DOCUMENTATION THESE |
| AGENCIES HAVE REVIEWED AND APPROVED |
| THE PLANS. |