Plan Review Notes
Plan Review Notes For Permit 99120645
Permit Number 99120645
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT COPY OF JOB SPECIFICATIONS AND
 COMPLETE PLUMBING DRAWINGS INCUDING
 ISOMETRICS FOR STORM,SANITARY,WATER AND
 ALL OTHER RELATED PLUMBING SYSTEMS PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 SUBMIT OCCUPANT LOAD PER SPC SEC.407.1.3
 TO ENSURE COMPLIANCE FOR MINIMUM REQD.
 SANITARY FACILITIES.
  
 SHT.C1.00-SHOW SQ.FT.AREA DRAINED BY
 EACH AREA DRAIN.COMPLY W/SPC TABLE
 1108.2.
  
 SHT.C2.00-LOCATION OF BFP DEVICE SHALL
 BE APPROVED BY CITY OF WPB UTILITIES.
 CALL 659-8000,EXT.2008.
  
 SHT.AO-11-SUBMIT DETAILS FOR RIVER ROCK
 FOUNTAIN.(FILL LINE,DRAINS,PUMP,ETC)PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 SHT.A1-1-REVISE PLBG.STANDARD AT CODE
 BRIEF TO READ 1994 ED.PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.101.1,101.2.
  
 FLOORS AND WALLS IN TOILET ROOMS/REST-
 ROMMS SHALL BE NONABSORBENT TO A HEIGHT
 OF 4' PER SBC SEC.1204.2.
  
 FLOOR DRAINS ARE REQD.IN ALL TOILET/
 RESTROOMS PER SPC SEC.409.4.1.1(SEE
 EXCEPTION).
  
 SUBMIT DETAILS FOR OVERFLOW DRAINAGE FOR
 ROOF STRUCTURE.COMPLY W/SBC 1517.6.4.1,
 THRU 1517.6.4.3.,1109.1- 1109.3.,AND
 APPENDIX "A"OF SPC.
  
 CLEARLY SHOW ALL RESTROOM/TOILET ROOM &
 TOILET STALL DIMENSIONS ON ARCH.FLOOR
 PLANS.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1,104.2.2.
  
 ALL HANDICAP TOILET STALLS SHALL CONTAIN
 AN ACCESSIBLE LAVATORY WITHIN THE STALL
 PER FACBC SEC.4.17.3(EXCEPTION:NEW
 CONSTRUCTION).
  
 ALL LOUNGE/BREAKROOM SINKS AND SINKS
 LOCATED IN OTHER NON-WORK AREAS SHALL
 BE FULLY ACCESSIBLE AND COMPLY W/FACBC
 SEC.4.24.1-4.24.7.
  
 CLEARLY SHOW DIMENSIONS (LXW)OF ALL
 SHOWER STALLS.SIZE OF ACCESSIBLE SHOWERS
 SHALL COMPLY W/FACBC SECS.4.21-4.21.8.
 OTHER SHOWERS SHALL BE ADAPTABLE PER
 FACBC SEC.4.1.3.(11).SEAT IN SHOWER
 SHALL COMPLY W/FACBC SEC.4.21.3.
  
 URINALS SHALL COMPLY W/FACBC SEC.4.18.1-
 4.18.4.
  
 FLUSH CONTROLS FOR WATER CLOSETS SHALL
 COMPLY W/FACBC SEC.4.16.5.
  
 DRINKING FOUNTAINS ARE REQD.PER SPC
 TABLE 407 AND ACCESSIBLE FOUNTAINS SHALL
 COMPLY W/FACBC SEC.4.1.3.(10)(A)(B).
  
 ACCESSIBLE WATER CLOSETS IN STALLS SHALL
 BE LOCATED IN THE CORNER,DIAGONAL TO THE
 DOOR PER FACBC SEC.4.17.3(EXCEPTION:NEW
 CONSTRUCTION).
  
 MEDICAL CARE FACILITIES SHALL COMPLY W/
 FACBC SECS.6.1(1).(10% RULE) AND 6.1(4)
 (A)(B),6.4.
  
 BATHTUBS IN ACCESSIBLE PATIENT ROOMS
 SHALL COMPLY W/FACBC SEC.4.20.1-4.20.7.
  
 CLEARLY SHOW WHEELCHAIR TURNING SPACE IN
 ACCESSIBLE TOILET ROOMS AND STALLS PER
 FACBC SEC.4.2.3.
  
 SHT.A6-2-SUBMIT U.L.ASSEMBLY NUMBERS FOR
 FIRE SAFING DETAILS PER SBC 701.5.2.
 (1996 ED.)AND SBC SEC.3502.
  
 SUBMIT COMPLETE INFO FOR SECONDARY ROOF
 DRAINAGE
  
 PLUMBING INSTALLATION SHALL COMPLY W/SPC
 APPENDIX "G"FOR HOSPITALS.
  
 MUTIPLE/GANG SHOWERS SHALL COMPLY W/SPC
 SEC.409.8.3.
 *****(SEE PLBG.STEP#2FOR CONTINUATION)**