Plan Review Notes
Plan Review Notes For Permit 99120645
Permit Number 99120645
Review Stop ENG
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PASSED WITH PROVISOS:
  
 STORMWATER COMMENTS:
  
 1.THE ENGINEER OF RECORD SHOULD PUT
 TOGETHER A LIST OF EXISTING IMPERVIOUS
 AND PERVIOUS AREAS AS WELL AS A LIST OF
 NEW IMPERVIOUS AND IMPERVIOUS ARES, TO
 SHOW WHAT THE NEW ERU RATE WILL BE.
 PLEASE SUBMIT PLANS SHOWING PRIOR TO
 DEMOLITION AND FINAL DESIGN SO WE CAN
 COMPARE THE TWO.
  
 4.THE STORMWATER SYSTEM ON THE HOSPITAL
 PROPERTY IS ALL PRIVATE AND AS SUCH WE
 HAVE NO COMMENTS ABOUT THE DESIGN,
 EXCEPT WHAT IS WRITTEN ABOVE.
  
 WATER AND SANITARY:
  
 1.ALL ON SITE PIPING IS A PRIVATE
 DISTRIBUTION SYSTEM METERED AND
 PROTECTED WITH BACKFLOW PREVENTERS AT
 45TH AND GREENWOOD AVENUES. ALL OF THE
 GRAVITY SYSTEM FROM 45TH STREET NORTH
 AND GREENWOOD WEST IS PRIVATE OWNED BY
 ST. MARY'S.AS SUCH WE DO NOT NEED TO
 REVIEW THIS DESIGN FOR COMPLIANCE TO OUR
 STANDARDS. BUT I MAKE THE FOLLOWING
 COMMENTS FOR ITEMS THAT I SEE AS
 POSSIBLY INCORRECT:
  
 2.A 4" METER IS SHOWN AT THE NORTHWEST
 CORNER OF THE BUILDING, IT IS NOT
 REQUIRED BY THE PUBLIC UTILITY
 DEPARTMENT SINCE WE MASTER METER THE
 SITE.
  
 3.SINCE ALL OF THE SANITARY SEWER SYSTEM
 IS A PRIVATE, ONE OWNER SYSTEM, A DEP
 PERMIT MAY NOT BE REQUIRED.CONTACT
 JAMES L. (DUTCH) HOLLAND, ENVIRONMENTAL
 ENGINEER (PLAN REVIEWER), AT
 W-561:355-4045, EX. 1134F-561:355-2442
 AND DISCUSS IT WITH HIM OR ONE OF THE
 OTHER PLAN REVIEWERS.
  
 4.THE FIRE LINE THAT COME OFF OF THE
 MASTER METERED DOMESTIC DISTRIBUTION
 MAIN DOES NOT APPEAR TO HAVE AN APPROVED
 DOUBLE CHECK BACKFLOW PREVENTER ON IT,
 IT SHOULD HAVE ONE TO STOP ANY WATER
 FROM COMING INTO THE SYSTEM WHEN PUMPED
 INTO THE FDC.PLEASE CHECK AND SEE IF
 EXISTS AND WAS LEFT OFF THE PLAN BY
 MISTAKE OR IF IT NEEDS TO BE ADDED.
  
 5.THE REDUCED PRESSURE BACKFLOW
 PREVENTER SHOWN IS A SINGLE DEVICE.WE
 STRONGLY SUGGEST ON DOMESTIC, CRITICAL
 USAGE LOCATIONS, SUCH AS THIS THAT TWO
 DEVICES ARE INSTALLED IN PARALLEL.THIS
 WAY IF ONE FAILS OR HAS TO BE SHUT OFF
 TO BE WORKED ON THE HOSPITAL IS NOT
 WITHOUT WATER.
  
 6.THE TEMPORARY JUMPER CONNECTION SHOWN
 ON PAGE C3.01 IS WRONG.TWO IN-LINE
 VALVES ARE REQUIRED WITH AN OPEN VENT
 BETWEEN.THIS ALLOWS WATER TO PASS THRU
 THE PROTECTED BYPASS FOR TESTING AND
 WITHOUT THE CHANCE OF BACKFLOW THRU THE
 SINGLE VALVE.THIS IS A DEP REQUIREMENT
 ALSO.