Plan Review Notes For Permit 99120507 |
Permit Number |
99120507 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | A DRINKING FOUNTAIN IS REQD.PER TABLE | | 407 OF SPC. | | | | PRIVATE BATHS SHALL BE HANDICAP | | ADAPTABLE PER FACBC SEC.4.1.3.(11). | | | | STAFF ROOM SINK SHALL COMPLY W/FACBC | | SEC.4.24.1.- 4.24.7. | | | | DRINKING FOUNTAIN SHALL COMPLY W/FACBC | | SEC.4.1.3.(10)(A). | | | | URINAL SHALL COMPLY W/FACBC SEC.4.18.2, | | THRU 4.18.4. | | | | MEN'S R.R.-STALL DOOR CANNOT SWING INTO | | CLEAR FLOOR SPACE FOR URINAL PER FACBC | | SEC.4.22.2. | | | | WALLS AND FLOORS IN TOILET ROOMS SHALL | | COMPLY W/SBC SEC.1204.2. | | | | WATER CLOSETS AND FIXTURE BRANCHES NOT | | PERMITTED ON WET VENTS PER COUNTYWIDE | | AMENDMENTS TO SPC SEC.911.1.1.(SEE | | PRIVATE TOILET ROOMS ON SANITARY RISER. | | | | MAX.OF 2 FIXTURES PERMITTED TO BE | | CONNECTED TO 1/2" C.W.AND 4 FIXTURES TO | | 1/2" H.W.PER COUNTYWIDE AMENDMENTS TO | | SPC SEC.607.7. | | | | WATER SUPPLY CONTROL SHALL COMPLY W/SPC | | SEC.610.4.1.,610.4.2. |
|