Plan Review Notes
Plan Review Notes For Permit 99120507
Permit Number 99120507
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00A DRINKING FOUNTAIN IS REQD.PER TABLE
 407 OF SPC.
  
 PRIVATE BATHS SHALL BE HANDICAP
 ADAPTABLE PER FACBC SEC.4.1.3.(11).
  
 STAFF ROOM SINK SHALL COMPLY W/FACBC
 SEC.4.24.1.- 4.24.7.
  
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).
  
 URINAL SHALL COMPLY W/FACBC SEC.4.18.2,
 THRU 4.18.4.
  
 MEN'S R.R.-STALL DOOR CANNOT SWING INTO
 CLEAR FLOOR SPACE FOR URINAL PER FACBC
 SEC.4.22.2.
  
 WALLS AND FLOORS IN TOILET ROOMS SHALL
 COMPLY W/SBC SEC.1204.2.
  
 WATER CLOSETS AND FIXTURE BRANCHES NOT
 PERMITTED ON WET VENTS PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.911.1.1.(SEE
 PRIVATE TOILET ROOMS ON SANITARY RISER.
  
 MAX.OF 2 FIXTURES PERMITTED TO BE
 CONNECTED TO 1/2" C.W.AND 4 FIXTURES TO
 1/2" H.W.PER COUNTYWIDE AMENDMENTS TO
 SPC SEC.607.7.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SEC.610.4.1.,610.4.2.