2001-01-08 00:00:00PROVIDE DESIGN CERTIFICATION FORM.
  
 PLAN S3,SPECIFYS THE INCORRECT CODE
 EDITION WAS USED.NOTE THE VALID CODE
 EDITION IS THE 1997 STANDARD BUILDING
 CODE.
  
 PROVIDE MANUAL J CALCULATIONS WITH THE
 ENERGY FORM.
  
 PROVIDE A DETAIL FOR ATTACHING THE
 WINDOW & DOOR SUB-BUCKS.
  
 PROVIDE PRODUCT APPROVAL FOR THE WINDOWS
 EXTERIOR DOORS, OVERHEAD GARAGE DOOR,
 ROOF TILES, FIREPLACE AND HURRICANE
 MISSLE IMPACT PROTECTION.SECT 1707.4 AME
  
 PLANS NEED PALM BEACH COUNTY IMPACT FEE
 REVIEW.
  
 SPECIFY ON S1 PLAN THAT ALL FOOTERS ARE
 REQUIRED TO BE A MININUM OF 12" BELOW
 GRADE. SECT 1804.1.3SBC 1997