2001-01-08 00:00:00 | ************** PROVISO **************** |
| |
| ***BEFORE FIRST INSPECTION SI CALLED IN* |
| |
| 1)NOTE:PLEASE CHECK REQ`MENTS FOR |
| KITCHEN OUTLETS FOR PENINSULAR AND |
| ISLAND AS PER ART: 210-52-C-2-3 |
| |
| 2)NOTE:ALSO AS PER 210-8-A-6 ALL OUTLETS |
| SERVING KITCHEN COUTNTERSPACE ARE TO BE |
| GFI /GFI PROTECTED. |
| |
| 3)NOTE:AS PER 210-52D 1996 NEC REQ`S |
| BATH(S) TO BE ON 20AMP DEDICATED CIRCUT. |
| NO LIGHTING IS TO BE PLACED ON BATH |
| CIRCUTS. |
| |
| 4)NOTE: AS PER 1993/1996 NFPA-72 |
| 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS!! |
| IF THEY ARE ROOMS WITH CLOSET SPACE THEN |
| THEY ARE TO ALSO MEET THE REQ`MENT. |
| |
| 5)NOTE: AS PER 250-81/215-5 NEED TO SHOW |
| COMPLETE GROUNDING ELECTRODE SYSTEM. |
| TO INCLUDE GROUND ROD,BLDG.STEEL AND |
| COLD WATER PIPE AS PART OF THE SYSTEM. |
| |
| 6)NOTE: NEEDTO SHOW CONDUCTOR SIZE OF |
| THE GROUNDING ELECTRODE. SIZE PER 250-94 |
| |
| 7)NOTE: NEED TO SHOW ALL CONDUCTORS FOR |
| SERVICE.!!! FROM METER TO PANELS. SHOW |
| CONDUIT SIZES. SHOW METER CAN SIZE. |
| IF THERE ARE TWO PANELS THEN SHOW TWO |
| FEEDS TO PANELS. PANEL B CANNOT BEFED |
| THROUGH PANEL A AS PER 373-8/215-5 |
| PLEASE INCLUDE GROUNDING CONDUTORS IN |
| ALL CONDUITS.EG. A/C FEEDS. |
| |
| 8)NOTE: NEED TO SUBMIT AIC RATING OF |
| ALL EQUIPMENT. TO INCLUDE MAINS AND |
| BRKRS. AIC IS FIGURED FROM FAULT CURRENT |
| CALCULATIONS. AS PER 110-9/215-5 |
| |
| PLEASE SUBMIT THE ABOVE FOR REVIEW AND |
| APPROVAL BEFORE FIRST ROUGH ELECTRICAL |
| INSPECTION IS CALLED IN. PLEASE SUBMIT |
| PLANS FOR NOTES :5,6,7,AND 8 WITHIN 20 |