2001-01-08 00:00:00************** PROVISO ****************
  
 ***BEFORE FIRST INSPECTION SI CALLED IN*
  
 1)NOTE:PLEASE CHECK REQ`MENTS FOR
 KITCHEN OUTLETS FOR PENINSULAR AND
 ISLAND AS PER ART: 210-52-C-2-3
  
 2)NOTE:ALSO AS PER 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUTNTERSPACE ARE TO BE
 GFI /GFI PROTECTED.
  
 3)NOTE:AS PER 210-52D 1996 NEC REQ`S
 BATH(S) TO BE ON 20AMP DEDICATED CIRCUT.
 NO LIGHTING IS TO BE PLACED ON BATH
 CIRCUTS.
  
 4)NOTE: AS PER 1993/1996 NFPA-72
 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS!!
 IF THEY ARE ROOMS WITH CLOSET SPACE THEN
 THEY ARE TO ALSO MEET THE REQ`MENT.
  
 5)NOTE: AS PER 250-81/215-5 NEED TO SHOW
 COMPLETE GROUNDING ELECTRODE SYSTEM.
 TO INCLUDE GROUND ROD,BLDG.STEEL AND
 COLD WATER PIPE AS PART OF THE SYSTEM.
  
 6)NOTE: NEEDTO SHOW CONDUCTOR SIZE OF
 THE GROUNDING ELECTRODE. SIZE PER 250-94
  
 7)NOTE: NEED TO SHOW ALL CONDUCTORS FOR
 SERVICE.!!! FROM METER TO PANELS. SHOW
 CONDUIT SIZES. SHOW METER CAN SIZE.
 IF THERE ARE TWO PANELS THEN SHOW TWO
 FEEDS TO PANELS. PANEL B CANNOT BEFED
 THROUGH PANEL A AS PER 373-8/215-5
 PLEASE INCLUDE GROUNDING CONDUTORS IN
 ALL CONDUITS.EG. A/C FEEDS.
  
 8)NOTE: NEED TO SUBMIT AIC RATING OF
 ALL EQUIPMENT. TO INCLUDE MAINS AND
 BRKRS. AIC IS FIGURED FROM FAULT CURRENT
 CALCULATIONS. AS PER 110-9/215-5
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW AND
 APPROVAL BEFORE FIRST ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. PLEASE SUBMIT
 PLANS FOR NOTES :5,6,7,AND 8 WITHIN 20
 DAYS OF RECIEPT OF NOTES. IF THERE ARE
 ANY QUESTIONS PLAESE CALL AT 659-8096
 EXT 8372