2001-01-08 00:00:00*************PROVISO********************
  
 1)NOTE:AS PER 215-5 IF THERE ARE GOING
 TO BE TWO DISCONNECTS? THEN YOU NEED
 TO HAVE THEM BOTH DRAWN ON PLANS.
  
 2)NOTE:AS PER ART;210-52D/215-5 PLEASE
 HAVE DEDICATED BATH(S) CIRCUT(S) SHOWN
 ON PANEL SCHED. NEEDS TO BE 20AMP #12
 AWG.
  
 3)NOTE:AS PER 250-81/215-5 NEED TO SHOW
 BLDG.STEEL AS PART OF THE GROUNDING
 ELECTRODE SYSTEM.
  
 4)NOTE;NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS/PANELS AS PER THE FOLLOW
 -ING NEC ARTS:110-9/230-65/215-5
 AIC RATING IS FIGURED FROM FAULT CURRENT
 CALCULATIONS.
  
 5)NOTE: AS NOTED BEFORE!! AS PER ART:
 373-8 PANELS/DISCONNECTS ETC ARE NOT TO
 BE USED AS RACEWAYS!!!!!!!!!!!!! THERE
 MUST BE AN ADDITIONAL CONDUIT FROM METER
 GOING TO SECOND DISC.!!!!!
 EACH COONDUIT MUST ONLY CONTAIN ONE SET
 OF CONDUCTORS.
  
 ****************************************
 ALL THE ABOVE INFORMATION NEEDS TO BE
 SUBMITTED FOR REVIEW AND APPROVAL
 BEFORE THE FIRST ROUGH ELECTRICAL
 INSPECTION IS CALLED IN!!!!! IF THERE
 ARE ANY QUESTIONS,,,CALL 659-8096 EXT.
 8372