2001-01-08 00:00:00 | *************PROVISO******************** |
| |
| 1)NOTE:AS PER 215-5 IF THERE ARE GOING |
| TO BE TWO DISCONNECTS? THEN YOU NEED |
| TO HAVE THEM BOTH DRAWN ON PLANS. |
| |
| 2)NOTE:AS PER ART;210-52D/215-5 PLEASE |
| HAVE DEDICATED BATH(S) CIRCUT(S) SHOWN |
| ON PANEL SCHED. NEEDS TO BE 20AMP #12 |
| AWG. |
| |
| 3)NOTE:AS PER 250-81/215-5 NEED TO SHOW |
| BLDG.STEEL AS PART OF THE GROUNDING |
| ELECTRODE SYSTEM. |
| |
| 4)NOTE;NEED TO SUBMIT AIC RATING OF |
| EQUIPMENT MAINS/PANELS AS PER THE FOLLOW |
| -ING NEC ARTS:110-9/230-65/215-5 |
| AIC RATING IS FIGURED FROM FAULT CURRENT |
| CALCULATIONS. |
| |
| 5)NOTE: AS NOTED BEFORE!! AS PER ART: |
| 373-8 PANELS/DISCONNECTS ETC ARE NOT TO |
| BE USED AS RACEWAYS!!!!!!!!!!!!! THERE |
| MUST BE AN ADDITIONAL CONDUIT FROM METER |
| GOING TO SECOND DISC.!!!!! |
| EACH COONDUIT MUST ONLY CONTAIN ONE SET |
| OF CONDUCTORS. |
| |
| **************************************** |
| ALL THE ABOVE INFORMATION NEEDS TO BE |
| SUBMITTED FOR REVIEW AND APPROVAL |
| BEFORE THE FIRST ROUGH ELECTRICAL |
| INSPECTION IS CALLED IN!!!!! IF THERE |
| ARE ANY QUESTIONS,,,CALL 659-8096 EXT. |
| 8372 |