2001-01-08 00:00:00 | ******************PROVISO*************** | | A CLEANOUT IS REQD.ON THE INLET TO | | INTERCEPTOR PER SPC SEC.710.4. | | | | FLOOR DRAIN IN LAUNDRY AREA SHALL BE A | | MIN.OF 3" PER SPC SEC.4.9.4.5 | | | | PLANS DON'T CORRELATE.ONE SET SHOWS F.D. | | IN LAUNDRY AREA, ONE DOES NOT.CLARIFY | | | | SUBMIT ADDITIONAL INFORMATION FROM | | MANUF.FOR TRAFFIC BEARING LINT TRAP. | | SUBMITTED INFORMATION IS VAGUE AS TO | | TRANSFERRAL OF IMPOSED LOADS ON TANK. | | SPC SEC.303.5. |
|