Notes |
Date |
Text |
2001-01-08 00:00:00 | | | SUBMIT UPDATED PRODUCT APPROVAL SHEETS | | FOR LINT TRAP.(APPROVAL EXPIRED 11/21/99 | | | | SUBMIT MANUF.SHEETS FOR H2O UNIT PER | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | | SUBMIT MANUF.SHEETS FOR GAS EQUIP.SGC | | SEC.402.1 | | | | FLOOR DRAIN IN BOILER EXCEEDS DISTANCE | | FROM VENT PER SPC 908.1. | | | | GALV.PIPE NOT PERMITTED U/G FOR WATER | | PIPE PER COUNTYWIDE AMENDMENTS TO SPC | | SEC.6.11.3.DELETE NOTE#12 ON P-3. | | | | WATER SUPPLY CONTROL SHALL COMPLY W/SPC | | SEC.610.4.1,610.4.2. | | | | SHOW LOCATION OF GAS METER.METER SHALL | | BE PROTECTED FROM DAMAGE.SGC 303. | | | | H.C.DRINKING FOUNTAIN SHALL COMPLY W/ | | FACBC SEC.4.1.3(10)(A)-PROVISIONS SHALL | | BE MADE FOR PEOPLE WHO HAVE TROUBLE | | BENDING OR STOOPING. |
|