Plan Review Notes
Plan Review Notes For Permit 99111358
Permit Number 99111358
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00 
 SUBMIT UPDATED PRODUCT APPROVAL SHEETS
 FOR LINT TRAP.(APPROVAL EXPIRED 11/21/99
  
 SUBMIT MANUF.SHEETS FOR H2O UNIT PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 SUBMIT MANUF.SHEETS FOR GAS EQUIP.SGC
 SEC.402.1
  
 FLOOR DRAIN IN BOILER EXCEEDS DISTANCE
 FROM VENT PER SPC 908.1.
  
 GALV.PIPE NOT PERMITTED U/G FOR WATER
 PIPE PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.6.11.3.DELETE NOTE#12 ON P-3.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SEC.610.4.1,610.4.2.
  
 SHOW LOCATION OF GAS METER.METER SHALL
 BE PROTECTED FROM DAMAGE.SGC 303.
  
 H.C.DRINKING FOUNTAIN SHALL COMPLY W/
 FACBC SEC.4.1.3(10)(A)-PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.